5.02021-11-25T12:35:18ZTemplates/ModulesTemplates/UPSPitONPitONTemplate Module ICMP PingTemplates/UPSBatteryConfigControlEnvironmentGeneralInputOutputTestThree phaseTrap- Number of manager to send trapsSNMP_AGENT.1.3.6.1.4.1.935.2.1.1.0XPPC-MIB.mconfigTrapsReceiversNum6hThe number of managers to send traps to.Trap
- Last replaced dateSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.1.3.0XPPC-MIB.upsBaseBatteryLastReplaceDate6h0TEXTThe date when the UPS system's batteries were last replaced in mm/dd/yy format. For UPS models, this value is originally set in the factory. When the UPS batteries are replaced, this value should be reset by the administrator.Battery
- Battery statusSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.1.1.0XPPC-MIB.upsBaseBatteryStatus5m30dThe status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsSmartConfigLowBatteryRunTime.BatteryXPPC-MIB::upsBaseBatteryStatus
- Battery time onSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.1.2.0XPPC-MIB.upsBaseBatteryTimeOnBattery5m30dsThe elapsed time in seconds since the UPS has switched to battery power.Battery
- Plugged devicesSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.1.1.0XPPC-MIB.upsBaseConfigNumDevices6hThe number of devices that are plugged into the UPS.Config
- Battery conserve controlSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.6.1.1.0XPPC-MIB.upsBaseControlConserveBattery5mSetting this variable to turnUpsOffToConserveBattery(2) causes a UPS on battery to be put into 'sleep' mode immediately. The (10) means suspending time(10 minutes) before turn off UPS. UPS will turn back on when utility power is restored. Attempting to turn off a UPS that is not on battery will result in a badValue error.
Setting this value to noTurnOffUps(1) has no effect.
The value noTurnOffUps(1) will always be returned when the variable is read.BatteryXPPC-MIB::upsBaseControlConserveBattery
- Model nameSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.1.1.1.0XPPC-MIB.upsBaseIdentModel6h30d0TEXTThe UPS model name (e.g. 'Intelligent 8000E 900VA').General
- UPS IDSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.1.1.2.0XPPC-MIB.upsBaseIdentUpsName6h30d0TEXTAn 8 byte ID string identifying the UPS. This object can be set by the administratorGeneral
- Input phaseSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.3.1.1.0XPPC-MIB.upsBaseInputPhase5mThe current AC input phase.Input
- Output phaseSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.1.2.0XPPC-MIB.upsBaseOutputPhase5mThe current output phase.Output
- Output statusSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.1.1.0XPPC-MIB.upsBaseOutputStatus5mThe current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1)OutputXPPC-MIB::upsBaseOutputStatus
- Eenvironment humiditySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.2.0XPPC-MIB.upsEnvHumidity5m%The environment humidity.Environment
- Environment over humiditySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.2.3.0XPPC-MIB.upsEnvOverHumidity5m%Alarm dupsAlarmOverHumidity on when the environment humidity over the value.Environment
- Environment over temperatureSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.2.1.0XPPC-MIB.upsEnvOverTemperature5m°CAlarm dupsAlarmOverTemperature on when the environment temperature over the value.Environment
- Environment security 1SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.5.0XPPC-MIB.upsEnvSecurity15mSecurity statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Environment security 2SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.6.0XPPC-MIB.upsEnvSecurity25mSecurity statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Environment security 3SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.7.0XPPC-MIB.upsEnvSecurity35mSecurity statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Environment security 4SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.8.0XPPC-MIB.upsEnvSecurity45mSecurity statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Environment security 5SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.9.0XPPC-MIB.upsEnvSecurity55mSecurity statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Environment security 6SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.10.0XPPC-MIB.upsEnvSecurity65mSecurity statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Environment security 7SNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.11.0XPPC-MIB.upsEnvSecurity75mSecurity statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Environment smokeSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.4.0XPPC-MIB.upsEnvSmoke5mSmoke statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Environment temperatureSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.1.0XPPC-MIB.upsEnvTemperature5m°CThe ambient environment temperature.Environment
- Environment under humiditySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.2.4.0XPPC-MIB.upsEnvUnderHumidity5m%Alarm dupsAlarmUnderHumidity on when the environment humidity below the valueEnvironment
- Environment under temperatureSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.2.2.0XPPC-MIB.upsEnvUnderTemperature5m°CAlarm dupsAlarmUnderTemperature on when the environment temperature below the value.Environment
- Environment waterSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.9.1.3.0XPPC-MIB.upsEnvWater5mWater statusEnvironmentXPPC-MIB::upsNormal/Abnormal
- Control ups offSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.6.2.1.0XPPC-MIB.upsSmaControlUpsOff5mSetting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state. The on/off switch on the UPS must be toggled for the UPS to return to operation.
Setting this value to noTurnUpsOff(1) has no effect.
The value noTurnUpsOff(1) will always be returned when the variable is read.ControlXPPC-MIB::upsSmartControlUpsOff
- Battery capacitySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.1.0XPPC-MIB.upsSmartBatteryCapacity5m%The remaining battery capacity expressed in percent of full capacity.Battery
- Battery current of maximum currentSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.7.0XPPC-MIB.upsSmartBatteryCurrent5m%The current battery current expressed in percent of maximum current.Battery
- Battery full charge voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.6.0XPPC-MIB.upsSmartBatteryFullChargeVoltage5mVThe fully charged battery voltage of the battery system used in the UPS, expressed in tenths of a volt.BatteryMULTIPLIER0.1
- Battery replace indicatorSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.5.0XPPC-MIB.upsSmartBatteryReplaceIndicator5mIndicates whether the UPS batteries need replacing.BatteryXPPC-MIB::upsSmartBatteryReplaceIndicator
- Battery time remainingSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.4.0XPPC-MIB.upsSmartBatteryRunTimeRemaining5msThe UPS battery run time remaining before battery exhaustion, in seconds.Battery
- Battery temperatureSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.3.0XPPC-MIB.upsSmartBatteryTemperature5m°CThe current internal UPS temperature expressed in tenths of a Celsius degree.BatteryMULTIPLIER0.1
- Battery current voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.2.2.2.0XPPC-MIB.upsSmartBatteryVoltage5mVDCThe current battery voltage expressed in 1/10 VDCBatteryMULTIPLIER0.1
- AlarmSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.4.0XPPC-MIB.upsSmartConfigAlarm5mA flag indicating how the UPS should handle audible line fail alarms.ConfigXPPC-MIB::upsSmartConfigAlarm
- Alarm timerSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.5.0XPPC-MIB.upsSmartConfigAlarmTimer5msThe time in seconds after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observerd only if the value of extControlAlarm is timed(2). Allowed values are 0 or 30 seconds.
If a value other than a supported value is provided in a set request, the UPS interprets it as a the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.Config
- Hight transfer voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.1.0XPPC-MIB.upsSmartConfigHighTransferVolt5mVACThe maximum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup.
Allowed value depend on the UPS used:
120 Volt units allow settings of 1290, 1320, 1350, 1380.
100 Volt units allow settings of 1080, 1100, 1120, 1140.
230 Volt units allow settings of 2530, 2640, 2710, 2800.
208 Volt units allow settings of 2240, 2290, 2340, 2390.
If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.ConfigMULTIPLIER0.1
- Low battery run timeSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.8.0XPPC-MIB.upsSmartConfigLowBatteryRunTime5msThe desired run time in seconds once the low battery condition is reached. Allowed values are 120, 300, 420, or 600 seconds. During this time the UPS will produce a constant warning tone which can not be disabled.
If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.Config
- Low transfer voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.3.0XPPC-MIB.upsSmartConfigLowTransferVol5mVACThe minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup.
Allowable values depend on the UPS used:
120 Volt units allow settings of 970, 1000, 1030, 1060.
100 Volt units allow settings of 810, 830, 850, 870.
230 Volt units allow settings of 1880, 1960, 2040, 2080.
208 Volt units allow settings of 1680, 1720, 1770, 1820.
If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.ConfigMULTIPLIER0.1
- Minimim return capacitySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.6.0XPPC-MIB.upsSmartConfigMinReturnCapacity5m%The minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS will not re-energize the output until the battery capacity is equal to this value. Allowed values are 0, 10, 25, or 90 percent.
If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.Config
- Rated output voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.1.0XPPC-MIB.upsSmartConfigRatedOutputVoltage5mVACThe nominal output voltage from the UPS in 1/10 VAC. Possible values are 1000, 1200, 2080, 2200, 2250, 2300 and 2400.
NOTE: Only units that are 2200, 2250, 2300 and 2400 can be changed. Allowable values are 2200, 2250, 2300 and 2400.
For these adjustable units, if a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used.ConfigMULTIPLIER0.1
- Return delaySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.9.0XPPC-MIB.upsSmartConfigReturnDelay5msThe delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UPS wakes up from 'sleep' mode. Allowed values are 0, 60, 180 and 300 seconds.
If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.Config
- SensitivitySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.7.0XPPC-MIB.upsSmartConfigSensitivity5mThe sensitivity of the UPS to utility line abnormalities or noises.ConfigXPPC-MIB::upsSmartConfigSensitivity
- Set EEPROM defaultsSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.12.0XPPC-MIB.upsSmartConfigSetEEPROMDefaults5mWRITE: Resets the UPS EEPROM variables to default values.
READ: returns 0Config
- Shut off delaySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.10.0XPPC-MIB.upsSmartConfigShutoffDelay5msThe delay in seconds the UPS remains on after being told to turn off. Allowed values are 12, 18, 24, 30, 36, 42, 48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and 600 seconds.
If a value other than a supported value is provided in a set request, the UPS interprets it as next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.Config
- UPS sleep timeSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.5.2.11.0XPPC-MIB.upsSmartConfigUpsSleepTime5mmThe time in minutes for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored.
This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station.
Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments.
If the provided value is higher than the highest acceptable value, the highest acceptable value is used.Config
- Control flash and beepSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.6.2.5.0XPPC-MIB.upsSmartControlFlashAndBeep5mUPS to identify itself by lighting all indicators and beeping.
Setting this variable to FlashAndBeep(2) causes the UPS lights all panel indicators and beeps.
Setting this value to noFlashAndBeep(1) has no effect.
The value noFlashAndBeep(1) will always be returned when the variable is read.ControlXPPC-MIB::upsSmartControlFlashAndBeep
- Control reboot upsSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.6.2.2.0XPPC-MIB.upsSmartControlRebootUps5mSetting this variable to rebootUps(2) causes the UPS to shut off and turn back on.
Setting this value to noRebootUps(1) has no effect.
The value noRebootUps(1) will always be returned when the variable is read.ControlXPPC-MIB::upsSmartControlRebootUps
- Control simulate power failSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.6.2.4.0XPPC-MIB.upsSmartControlSimulatePowerFail5mSetting this variable to simulatePowerFailure(2) causes the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no effect.
The value noSimulatePowerFailure(1) will always be returned when the variable is read.ControlXPPC-MIB::upsSmartControlSimulatePowerFail
- Control turn on ups loadSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.6.2.6.0XPPC-MIB.upsSmartControlTurnOnUpsLoad5mSetting this variable to upsSmartControlTurnOnUpsLoad(2) causes the UPS switch back to utility power if utility power is present.
Setting this value to noUpsSmartControlTurnOnUpsLoad(1) has no effect.
The value noUpsSmartControlTurnOnUpsLoad(1) will always be returned when the variable is read.ControlXPPC-MIB::upsSmartControlTurnOnUpsLoad
- Control ups sleepSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.6.2.3.0XPPC-MIB.upsSmartControlUpsSleep5mSetting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsSmartConfigUpsSleepTime.
When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored.
Setting this value to noPutUpsToSleep(1) has no effect.
The value noPutUpsToSleep(1) will always be returned when the variable is read.ControlXPPC-MIB::upsSmartControlUpsSleep
- SNMP Proxy agent firmware revisionSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.1.2.4.0XPPC-MIB.upsSmartIdentAgentFirmwareRevision6h30d0TEXTThe firmware revision of the UPS SNMP Proxy agent.General
- Manufactured dateSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.1.2.2.0XPPC-MIB.upsSmartIdentDateOfManufacture6h30d0TEXTThe date when the UPS was manufactured in mm/dd/yy format.General
- Firmware revisionSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.1.2.1.0XPPC-MIB.upsSmartIdentFirmwareRevision6h30d0TEXTThe firmware revision of the UPS system.General
- Serial numberSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.1.2.3.0XPPC-MIB.upsSmartIdentUpsSerialNumber6h30d0TEXTAn 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS.General
- Input frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.3.2.4.0XPPC-MIB.upsSmartInputFrequency5mHzThe current input frequency to the UPS system in 1/10 Hz.InputMULTIPLIER0.1
- Input line fail causeSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.3.2.5.0XPPC-MIB.upsSmartInputLineFailCause5mThe reason for the occurrence of the last transfer to UPS battery power. The variable is set to noTransfer(1) if there is no transfer yet. The variable is set to highLineVoltage(2) if the transfer to battery is caused by an over voltage greater than the high transfer voltage. The variable is set to brownout(3) if the duration of the outage is greater than five seconds and the line voltage is between 40 percent of the rated output voltage and the low transfer voltage. The variable is set to blackout(4) if the duration of the outage is greater than five seconds and the line voltage is between 40 percent of the rated output voltage and ground. The variable is set to smallMomentarySag(5) if the duration of the outage is less than five seconds and the line voltage is between 40 percent of the rated output voltage and the low transfer voltage. The variable is set to deepMomentarySag(6) if the duration of the outage is less than five seconds and the line voltage is between 40 percent of the rated output voltage and ground.InputXPPC-MIB::upsSmartInputLineFailCause
- Input line voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.3.2.1.0XPPC-MIB.upsSmartInputLineVoltage5mVACThe current utility line voltage in 1/10 VACInputMULTIPLIER0.1
- Input maximum line voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.3.2.2.0XPPC-MIB.upsSmartInputMaxLineVoltage5mVACThe maximum utility line voltage in 1/10 VAC over the previous 1 minute period.InputMULTIPLIER0.1
- Input minimum line voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.3.2.3.0XPPC-MIB.upsSmartInputMinLineVoltage5mVACThe minimum utility line voltage in 1/10 VAC over the previous 1 minute period.InputMULTIPLIER0.1
- Output frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.2.2.0XPPC-MIB.upsSmartOutputFrequency5mHzThe current output frequency of the UPS system in 1/10 Hz.OutputMULTIPLIER0.1
- Output loadSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.2.3.0XPPC-MIB.upsSmartOutputLoad5m%The current UPS load expressed in percent of rated capacity.Output
- Output voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.4.2.1.0XPPC-MIB.upsSmartOutputVoltage5mVACThe output voltage of the UPS system in 1/10 VAC.OutputMULTIPLIER0.1
- Test calibration dateSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.7.2.8.0XPPC-MIB.upsSmartTestCalibrationDate6h0TEXTThe date the last UPS runtime calibration was performed in mm/dd/yy format.Test
- Test calibration resultsSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.7.2.7.0XPPC-MIB.upsSmartTestCalibrationResults5mThe results of the last runtime calibration.
Value ok(1) means a successful runtime calibration.
Value invalidTest(2) indicates last calibration did not take place since the battery capacity was below 100 percent.
Value calibrationInProgress(3) means a calibration is occurring now.TestXPPC-MIB::upsSmartTestCalibrationResults
- Test diagnosticsSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.7.2.2.0XPPC-MIB.upsSmartTestDiagnostics5mSetting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test.
Setting this value to noTestDiagnostics(1) has no effect.
The value noTestDiagnostics(1) will always be returned when the variable is read.TestXPPC-MIB::upsSmartTestDiagnosticSchedule
- Test diagnostic scheduleSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.7.2.1.0XPPC-MIB.upsSmartTestDiagnosticSchedule5mThe UPS system's automatic battery test schedule.TestXPPC-MIB::upsSmartTestDiagnosticSchedule
- Diagnostics resultsSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.7.2.3.0XPPC-MIB.upsSmartTestDiagnosticsResults5mThe results of the last UPS diagnostics test performed.TestXPPC-MIB::upsSmartTestDiagnosticsResults
- Test indicatorsSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.7.2.5.0XPPC-MIB.upsSmartTestIndicators5mSetting this variable to testIndicators(2) causes the UPS to perform a front panel indicator (lights) test.
Setting this value to noTestIndicators(1) has no effect.
The value noTestIndicators(1) will always be returned when the variable is read.TestXPPC-MIB::upsSmartTestIndicators
- Last diagnostics dateSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.7.2.4.0XPPC-MIB.upsSmartTestLastDiagnosticsDate6h0TEXTThe date the last UPS diagnostics test was performed in mm/dd/yy format.Test
- Test runtime calibrationSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.7.2.6.0XPPC-MIB.upsSmartTestRuntimeCalibration5mSetting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100 percent. The test runs until capacity is less than 25 percent.
Setting this variable to cancelCurrentCalibration(3) after setting performCalibration(2) will cancel the current discharge.
Setting this variable to noPerformCalibration(1) will have no effect.
The value noPerformCalibration(1) will always be returned when the variable is read.
The result of the calibration will be saved in upsSmartTestCalibrationResult.TestXPPC-MIB::upsSmartTestRuntimeCalibration
- Phase battery capacity percentageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.1.2.0XPPC-MIB.upsThreePhaseBatteryCapacityPercentage5m%Battery Capacity PercentageBattery
- Three phase battery currentSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.1.4.0XPPC-MIB.upsThreePhaseBatteryCurrent5mBattery Electric CurrentThree phase
- Three phase battery temperatureSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.1.5.0XPPC-MIB.upsThreePhaseBatteryTemperature5m°CBattery TemperatureThree phaseMULTIPLIER0.1
- Three phase battery time remainSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.1.3.0XPPC-MIB.upsThreePhaseBatteryTimeRemain5mmBattery Time Remain (unit is Minute)Three phase
- Three Phase Battery VoltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.1.1.0XPPC-MIB.upsThreePhaseBatteryVoltage5mVBattery VoltageThree phase
- Three phase bypass source frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.4.1.0XPPC-MIB.upsThreePhaseBypassSourceFrequency5mHzBypass FrequencyThree phaseMULTIPLIER0.1
- Three phase bypss source voltage RSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.4.2.0XPPC-MIB.upsThreePhaseBypssSourceVoltageR5mVBypass VoltageRThree phase
- Three phase bypss source voltage SSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.4.3.0XPPC-MIB.upsThreePhaseBypssSourceVoltageS5mVBypass VoltageSThree phase
- Three phase bypss source voltage TSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.4.4.0XPPC-MIB.upsThreePhaseBypssSourceVoltageT5mVBypass VoltageTThree phaseMULTIPLIER0.1
- Three phase DC and rectifier status battery statusSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.5.5.0XPPC-MIB.upsThreePhaseDCandRectifierStatusBatteryStatus5mBack StatusThree phaseXPPC-MIB::upsThreePhaseDCandRectifierStatusBatteryStatus
- Three phase DC and rectifier status charge statusSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.5.6.0XPPC-MIB.upsThreePhaseDCandRectifierStatusChargeStatus5mCharge StatusThree phaseXPPC-MIB::upsThreePhaseDCandRectifierStatusChargeStatus
- Three phase DC and rectifier status in and outSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.5.4.0XPPC-MIB.upsThreePhaseDCandRectifierStatusInAndOut5mIn And PutThree phaseXPPC-MIB::upsThreePhaseDCandRectifierStatusInAndOut
- Three phase DC and rectifier status low batterySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.5.3.0XPPC-MIB.upsThreePhaseDCandRectifierStatusLowBattery5mLow BatteryThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase DC and rectifier status low battery shutdownSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.5.2.0XPPC-MIB.upsThreePhaseDCandRectifierStatusLowBatteryShutdown5mLow Battery ShutdownThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase DC and rectifier status rectifier operatingSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.5.7.0XPPC-MIB.upsThreePhaseDCandRectifierStatusRecOperating5mRectifier OperatinThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase DC and rectifier status rectifier rotation errorSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.5.1.0XPPC-MIB.upsThreePhaseDCandRectifierStatusRecRotError5mRectifier Rotation ErrorThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase fault status bypass breakerSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.7.3.0XPPC-MIB.upsThreePhaseFaultStatusBypassBreaker5mBypass BreakerThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase fault status emergency stopSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.7.1.0XPPC-MIB.upsThreePhaseFaultStatusEmergencyStop5mEmergency StopThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase fault status high DC shutdownSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.7.2.0XPPC-MIB.upsThreePhaseFaultStatusHighDCShutdown5mHigh DC ShutdownThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase fault status inverter output failSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.7.5.0XPPC-MIB.upsThreePhaseFaultStatusInverterOutputFail5mOutput FailThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase fault status overLoadSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.7.4.0XPPC-MIB.upsThreePhaseFaultStatusOverLoad5mOver LoadThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase fault status over temperatureSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.7.6.0XPPC-MIB.upsThreePhaseFaultStatusOverTemperature5mOver TemperatureThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase fault status short circuitSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.7.7.0XPPC-MIB.upsThreePhaseFaultStatusShortCircuit5mShort CircuitThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase input frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.2.1.0XPPC-MIB.upsThreePhaseInputFrequency5mHzInput FrequencyThree phaseMULTIPLIER0.1
- Three phase input voltage RSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.2.2.0XPPC-MIB.upsThreePhaseInputVoltageR5mVInput VoltageRThree phase
- Three phase input voltage SSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.2.3.0XPPC-MIB.upsThreePhaseInputVoltageS5mVInput VoltageSThree phase
- Three phase input voltage TSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.2.4.0XPPC-MIB.upsThreePhaseInputVoltageT5mVInput VoltageTThree phase
- Three phase output frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.3.1.0XPPC-MIB.upsThreePhaseOutputFrequency5mHzOutput FrequencyThree phaseMULTIPLIER0.1
- Three phase output load percentage RSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.3.5.0XPPC-MIB.upsThreePhaseOutputLoadPercentageR5m%Load PercentageRThree phaseMULTIPLIER0.1
- Three phase output load percentage SSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.3.6.0XPPC-MIB.upsThreePhaseOutputLoadPercentageS5m%Load PercentageSThree phaseMULTIPLIER0.1
- Three phase output load percentage TSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.3.7.0XPPC-MIB.upsThreePhaseOutputLoadPercentageT5m%Load PercentageTThree phase
- Three phase output voltage RSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.3.2.0XPPC-MIB.upsThreePhaseOutputVoltageR5mVOutput VoltageRThree phase
- Three phase output voltage SSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.3.3.0XPPC-MIB.upsThreePhaseOutputVoltageS5mVOutput VoltageSThree phase
- Three phase output voltage TSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.3.4.0XPPC-MIB.upsThreePhaseOutputVoltageT5mVOutput VoltageTThree phase
- Three phase rating battery voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.8.7.0XPPC-MIB.upsThreePhaseRatingBatteryVoltage5mVBattery VoltageThree phase
- Three phase rating bypass frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.8.4.0XPPC-MIB.upsThreePhaseRatingBypassFrequency5m0TEXTBypass FrequencyThree phase
- Three phase rating bypass voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.8.3.0XPPC-MIB.upsThreePhaseRatingBypassVoltage5mBypass VoltageThree phase
- Three phase rating output frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.8.6.0XPPC-MIB.upsThreePhaseRatingOutputFrequency5mHzOutput FrequencyThree phase
- Three phase rating output voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.8.5.0XPPC-MIB.upsThreePhaseRatingOutputVoltage5m0TEXTOutput VoltageThree phase
- Three phase rating powerSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.8.8.0XPPC-MIB.upsThreePhaseRatingPower5m0TEXTPower RatingThree phase
- Three phase rating rectifier frequencySNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.8.2.0XPPC-MIB.upsThreePhaseRatingRectifierFrequency5mHzRectifier FrequencyThree phase
- Three phase rating rectifier voltageSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.8.1.0XPPC-MIB.upsThreePhaseRatingRectifierVoltage5m0TEXTRectifier VoltageThree phase
- Three phase UPS static switch modeSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.6.4.0XPPC-MIB.upsThreePhaseUPSStaticSwitchMode5mSwitch ModeThree phaseXPPC-MIB::upsThreePhaseUPSStaticSwitchMode
- Three phase UPS status AC statusSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.6.3.0XPPC-MIB.upsThreePhaseUPSStatusACStatus5mAC StatusThree phaseXPPC-MIB::upsThreePhaseUPSStatusACStatus
- Three phase UPS status bypass frequency failSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.6.1.0XPPC-MIB.upsThreePhaseUPSStatusBypassFreqFail5mBypass StatusThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase UPS status inverter operatingSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.6.5.0XPPC-MIB.upsThreePhaseUPSStatusInverterOperating5mOperatingThree phaseXPPC-MIB::upsThreePhaseDCandRectifierYes/No
- Three phase UPS status manual bypass breakerSNMP_AGENT.1.3.6.1.4.1.935.1.1.1.8.6.2.0XPPC-MIB.upsThreePhaseUPSStatusManualBypassBreaker5mBreaker StatusThree phaseXPPC-MIB::upsThreePhaseUPSStatusManualBypassBreaker
DevicesSNMP_AGENTdiscovery[{#UPSDEVICEID},1.3.6.1.4.1.935.1.1.1.5.1.2.1.1,{#UPSDEVICENAME},1.3.6.1.4.1.935.1.1.1.5.1.2.1.2]XPPC-MIB.indexOfDevice1hDiscovery pluged devicesDevice {#UPSDEVICENAME} acceptSNMP_AGENT1.3.6.1.4.1.935.1.1.1.5.1.2.1.4.{#UPSDEVICEID}XPPC-MIB[deviceAccept.{#UPSDEVICEID}]5mAn entry is added if yes, the entry is deleted if no.ConfigXPPC-MIB::yes/noDevice {#UPSDEVICENAME} idSNMP_AGENT1.3.6.1.4.1.935.1.1.1.5.1.2.1.1.{#UPSDEVICEID}XPPC-MIB[nameOfDevice.{#UPSDEVICEID}]6h0TEXTThe index of the device that is plugged into the UPS.ConfigDevices {#UPSDEVICENAME} ratingSNMP_AGENT1.3.6.1.4.1.935.1.1.1.5.1.2.1.3.{#UPSDEVICEID}XPPC-MIB[vaRatingOfDevice.{#UPSDEVICEID}]5mThe volt-amp rating of the device plugged into the UPSConfigTrapsSNMP_AGENTdiscovery[{#TRAPID},1.3.6.1.4.1.935.2.1.2.1.1]XPPC-MIB.trapsIndex1hDiscovery trapsReceiver {#TRAPID} acceptSNMP_AGENT1.3.6.1.4.1.935.2.1.2.1.5.{#TRAPID}XPPC-MIB[receiverAccept.{#TRAPID}]5mAn entry will become active if yes, and will be deleted if no.TrapXPPC-MIB::yes/noReceiver {#TRAPID} community stringSNMP_AGENT1.3.6.1.4.1.935.2.1.2.1.3.{#TRAPID}XPPC-MIB[receiverCommunityString.{#TRAPID}]6h0TEXTThe community name to use in the trap when sent to the manager.TrapSeverity level {#TRAPID}SNMP_AGENT1.3.6.1.4.1.935.2.1.2.1.4.{#TRAPID}XPPC-MIB[severityLevel.{#TRAPID}]5mThe severity threshold of traps to send to the manager. Traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager.TrapXPPC-MIB::severityLevelTrap {#TRAPID} receiver addressSNMP_AGENT1.3.6.1.4.1.935.2.1.2.1.2.{#TRAPID}XPPC-MIB[trapsReceiverAddr.{#TRAPID}]6h0TEXTThe IP address of the manager to send a trap to.Trap{$CRITICAL_BATTERY_TIME}20m{$CRITYICAL_BATTERY_CAPACITY}50Template Module ICMP PingTemplate Module ICMP PingTemplate Module ICMP Ping version: 0.12Templates/ModulesStatus- ICMP pingSIMPLEicmpping601wStatusService state{max(#3)}=0Unavailable by ICMP pingHIGHLast value: {ITEM.LASTVALUE1}.
Last three attempts returned timeout. Please check device connectivity.
- ICMP lossSIMPLEicmppingloss601wFLOAT%Status{min(5m)}>{$ICMP_LOSS_WARN} and {min(5m)}<100High ICMP ping lossWARNINGUnavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
- ICMP response timeSIMPLEicmppingsec601wFLOATsStatus{avg(5m)}>{$ICMP_RESPONSE_TIME_WARN}High ICMP ping response timeWARNINGHigh ICMP ping loss{Template Module ICMP Ping:icmppingloss.min(5m)}>{$ICMP_LOSS_WARN} and {Template Module ICMP Ping:icmppingloss.min(5m)}<100Unavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
{$ICMP_LOSS_WARN}20{$ICMP_RESPONSE_TIME_WARN}0.15Service state0Down1UpXPPC-MIB::severityLevel1information2warning3severeXPPC-MIB::upsBaseBatteryStatus1unknown2batteryNormal3batteryLowXPPC-MIB::upsBaseControlConserveBattery1noTurnOffUps2turnUpsOffToConserveBattery3turnUpsOffToConserveBatteryDelayXPPC-MIB::upsBaseOutputStatus1unknown2onLine3onBattery4onBoost5sleeping6onBypass7rebooting8standBy9onBuckXPPC-MIB::upsNormal/Abnormal1normal2abnormalXPPC-MIB::upsSmartBatteryReplaceIndicator1noBatteryNeedsReplacing2batteryNeedsReplacingXPPC-MIB::upsSmartConfigAlarm1timed2atLowBattery3neverXPPC-MIB::upsSmartConfigSensitivity1auto2low3medium4highXPPC-MIB::upsSmartControlFlashAndBeep1noFlashAndBeep2flashAndBeepXPPC-MIB::upsSmartControlRebootUps1noRebootUps2rebootUpsXPPC-MIB::upsSmartControlSimulatePowerFail1noSimulatePowerFailure2simulatePowerFailureXPPC-MIB::upsSmartControlTurnOnUpsLoad1noUpsSmartControlTurnOnUpsLoad2upsSmartControlTurnOnUpsLoadXPPC-MIB::upsSmartControlUpsOff1noTurnUpsOff2turnUpsOffXPPC-MIB::upsSmartControlUpsSleep1noPutUpsToSleep2putUpsToSleepXPPC-MIB::upsSmartInputLineFailCause1noTransfer2highLineVoltage3brownout4blackout5smallMomentarySag6deepMomentarySag7smallMomentarySpike8largeMomentarySpikeXPPC-MIB::upsSmartTestCalibrationResults1ok2invalidTest3calibrationInProgressXPPC-MIB::upsSmartTestDiagnosticSchedule1unknown2biweekly3weekly4neverXPPC-MIB::upsSmartTestDiagnosticsResults1ok2failed3invalidTest4testInProgressXPPC-MIB::upsSmartTestIndicators1noTestIndicators2testIndicatorsXPPC-MIB::upsSmartTestRuntimeCalibration1noPerformCalibration2performCalibration3cancelCurrentCalibrationXPPC-MIB::upsThreePhaseDCandRectifierStatusBatteryStatus4backup5acnormalXPPC-MIB::upsThreePhaseDCandRectifierStatusChargeStatus6boost7float16noXPPC-MIB::upsThreePhaseDCandRectifierStatusInAndOut2threeInOneOut3threeInThreeOutXPPC-MIB::upsThreePhaseDCandRectifierYes/No14yes16noXPPC-MIB::upsThreePhaseUPSStaticSwitchMode12invermode13bypassmodeXPPC-MIB::upsThreePhaseUPSStatusACStatus10normal11abnormalXPPC-MIB::upsThreePhaseUPSStatusManualBypassBreaker8close9openXPPC-MIB::yes/no1yes2no