5.02021-11-21T22:07:09ZTemplatesPowertek 1 Phase PDUPowertek 1 Phase PDU## Description
Created by Joakim Kingström at Sports Interactive.
## Overview
This template is for Powertek 1-phase PDU's.
It consists of 25 Items, nine triggers, and four graphs. It also has four discovery rules, with one of them having nine trigger prototypes. The discovery rules are disabled by default since they only created noise for me, but might be useful for other people.
## Author
Joakim Kingström
TemplatesPWT_1phase_MIB- Software versionSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.1.1.0.1.3.6.1.4.1.42610.1.4.4.1.1.1.01h0TEXTThe firmware version of the device.PWT_1phase_MIB
- Serial numberSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.1.2.0.1.3.6.1.4.1.42610.1.4.4.1.1.2.01h0TEXTA Model of this device.PWT_1phase_MIB
- IP AddressSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.1.0.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.1.01h0TEXTThe ip address that NMS can identify the managed device.PWT_1phase_MIB
- GatewaySNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.2.0.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.2.01h0TEXTThe default gateway that allow device managed through routers.PWT_1phase_MIB
- IPv4 SubnetSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.3.0.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.3.01h0TEXTInternet address subnet maskPWT_1phase_MIB
- Primary DNSSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.4.0.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.4.01h0TEXTInternet address of Primary DNS ServerPWT_1phase_MIB
- Secondary DNSSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.5.0.1.3.6.1.4.1.42610.1.4.4.1.2.1.2.5.01h0TEXTInternet address of Secondary DNSPWT_1phase_MIB
- System NameSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.3.1.0.1.3.6.1.4.1.42610.1.4.4.1.3.1.01h0TEXTThe name of system.PWT_1phase_MIB
- System ContactSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.3.2.0.1.3.6.1.4.1.42610.1.4.4.1.3.2.01h0TEXTThe contact of system.PWT_1phase_MIB
- System LocationSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.3.3.0.1.3.6.1.4.1.42610.1.4.4.1.3.3.01h0TEXTThe location of system.PWT_1phase_MIB
- System TimeSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.3.6.1.0.1.3.6.1.4.1.42610.1.4.4.1.3.6.1.01h0TEXTThe date/time in agentPWT_1phase_MIB
- NTP ServerSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.3.6.7.2.0.1.3.6.1.4.1.42610.1.4.4.1.3.6.7.2.01h0TEXTThe ip address of NTP server.PWT_1phase_MIB
- SNMP PortSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.4.2.0.1.3.6.1.4.1.42610.1.4.4.1.4.2.01hFLOATThe UDP port for SNMP.PWT_1phase_MIB
- SNMP versionSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.4.3.0.1.3.6.1.4.1.42610.1.4.4.1.4.3.01hFLOATSet SNMP version.PWT_1phase_MIB
- SMTP ServerSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.5.1.0.1.3.6.1.4.1.42610.1.4.4.1.5.1.01h0TEXTThe address of Email server.PWT_1phase_MIB
- SMTP PortSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.5.2.0.1.3.6.1.4.1.42610.1.4.4.1.5.2.01hFLOATThe UDP port for Email Server.PWT_1phase_MIB
- Email sender addressSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.5.3.0.1.3.6.1.4.1.42610.1.4.4.1.5.3.01h0TEXTThe sender\'s Email addressPWT_1phase_MIB
- Email PrefixSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.5.4.0.1.3.6.1.4.1.42610.1.4.4.1.5.4.01h0TEXTThe prefix string of mail subjectPWT_1phase_MIB
- Active PowerSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1FLOATWThe power that the PDU is currently using.PWT_1phase_MIBMULTIPLIER0.1{last()}>4600{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 4.6 kWHIGHThe power used currently is more than 4.6 kW.{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 5.8 kW{Powertek 1 Phase PDU:.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1.last()}>5800{last()}>5800{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 5.8 kWDISASTERThe power used currently is more than 5.8 kW.
- PDU Reset DateSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.1.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.110m0TEXTThe reset date of the PDU.PWT_1phase_MIB{diff()}=1{#SNMPVALUE} {ITEM.LASTVALUE} :: PDU Reset Date changedWARNINGThe PDU reset has changed, indicating that the PDU has been switched off and on.
- Energy usedSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4.1.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4.11hFLOATWThe total energy used by the PDU.PWT_1phase_MIB
- AmpsSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1FLOATAThe amps currently used by the PDU.PWT_1phase_MIBMULTIPLIER0.01{last()}>13{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 13AHIGHThe PDU is currently using more than 13 Amps.{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 16A{Powertek 1 Phase PDU:.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1.last()}>16{last()}>16{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 16ADISASTERThe PDU is currently using more than 16 Amps.
- PDU Inlet VoltageSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9.1.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9.1FLOATVThe current voltage of the PDU.PWT_1phase_MIB
- VoltageSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1FLOATVThe Voltage of the PDU.PWT_1phase_MIBMULTIPLIER0.1{last()}>245{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 245VHIGHThe voltage of the PDU is currently more than 245V, which is too high.{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 250V{Powertek 1 Phase PDU:.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1.last()}>250{last()}>250{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 250VDISASTERThe voltage of the PDU is currently more than 250V, which is too high.
- PDU Power FactorSNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.1.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.11hDISABLEDFLOAT%The power factor of the PDU indicates how much of the power is actually used.PWT_1phase_MIBMULTIPLIER0.1{last()}<90{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 90%DISASTERThe power factor of the PDU is currently less than 90% which indicates power is leaking and not being used.{last()}<95{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 95%HIGHThe power factor of the PDU is currently less than 95% which indicates power is leaking and not being used.{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 90%{Powertek 1 Phase PDU:.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.1.last()}<90
SPSv1-MIB::pduSnmpTrapsReceiversTableSNMP_AGENTdiscovery[{#TRAPSRECEIVERADDR},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2,{#RECEIVEREVENTLEVEL},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3,{#RECEIVERSNMPVER},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4,{#RECEIVERDESCRIPTION},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5].1.3.6.1.4.1.42610.1.4.4.1.4.43600DISABLEDA list of managers to send traps to. The number of
entries is given by the value of pduSnmpNumTrapReceiversSPSv1-MIB::trapsReceiverAddr[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2.[{#SNMPINDEX}]1h2w0TEXTThe IP address of the manager to send a trap to.PWT_1phase_MIBSPSv1-MIB::receiverEventLevel[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3.[{#SNMPINDEX}]1h2w0FLOATThe severity level of traps to be received by this manager.PWT_1phase_MIBSPSv1-MIB::receiverEventLevelSPSv1-MIB::receiverSnmpVer[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4.[{#SNMPINDEX}]1h2w0FLOATThe SNMP Trap version of trap receivers.PWT_1phase_MIBSPSv1-MIB::receiverSnmpVerSPSv1-MIB::receiverDescription[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5.[{#SNMPINDEX}]1h2w0TEXTDescription of trap receiversPWT_1phase_MIBSPSv1-MIB::pduEmailReceiversTableSNMP_AGENTdiscovery[{#TRAPSRECEIVERADDR},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2,{#RECEIVEREVENTLEVEL},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3,{#RECEIVERSNMPVER},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4,{#RECEIVERDESCRIPTION},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5,{#INLETCFGLOADCRITICAL},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2,{#INLETCFGLOADWARNING},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3,{#INLETCFGCURRCRITPHASE1},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4,{#INLETCFGCURRCRITPHASE2},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5].1.3.6.1.4.1.42610.1.4.4.1.5.83600DISABLEDA list of managers to send email notification to.SPSv1-MIB::mailRecvReceiverAddr[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.2.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.2.[{#SNMPINDEX}]1h2w0TEXTThe Email address of the manager to send a email notification to.PWT_1phase_MIBSPSv1-MIB::mailRecvEmailType[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.3.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.3.[{#SNMPINDEX}]1h2w0FLOATThe Email Type of email notification receivers.PWT_1phase_MIBSPSv1-MIB::mailRecvEmailTypeSPSv1-MIB::mailRecvEventLevel[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.4.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.4.[{#SNMPINDEX}]1h2w0FLOATThe severity level of email notification to be received by this manager.PWT_1phase_MIBSPSv1-MIB::mailRecvEventLevelSPSv1-MIB::mailRecvDescription[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.5.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.5.[{#SNMPINDEX}]1h2w0TEXTDescription of email notification receiversPWT_1phase_MIBSPSv1-MIB::pduPwrMonitoringInletStatusTableSNMP_AGENTdiscovery[{#TRAPSRECEIVERADDR},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2,{#RECEIVEREVENTLEVEL},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3,{#RECEIVERSNMPVER},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4,{#RECEIVERDESCRIPTION},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5,{#INLETCFGLOADCRITICAL},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2,{#INLETCFGLOADWARNING},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3,{#INLETCFGCURRCRITPHASE1},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4,{#INLETCFGCURRCRITPHASE2},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5].1.3.6.1.4.1.42610.1.4.4.1.6.1.23600DISABLEDA list to display status of Inlet.Active Power[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.[{#SNMPINDEX}]1h2w0DISABLEDFLOATWThe total power of inlet.PWT_1phase_MIBMULTIPLIER0.1{last()}>4.6{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 4.6 kWDISABLEDHIGHThe power used currently is more than 4.6 kW.{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 5.8 kW{Powertek 1 Phase PDU:.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.[{#SNMPINDEX}].last()}>5.8{last()}>5.8{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 5.8 kWDISABLEDDISASTERThe power used currently is more than 5.8 kW.PDU Reset Date[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.[{#SNMPINDEX}]1h2w0DISABLEDTEXTThe reset date of inlet.PWT_1phase_MIB{diff()}=1{#SNMPVALUE} {ITEM.LASTVALUE} :: PDU Reset Date changedDISABLEDWARNINGThe PDU reset has changed, indicating that the PDU has been switched off and on.Energy used[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4.[{#SNMPINDEX}]1h2w0DISABLEDFLOATWThe total energy of inlet.PWT_1phase_MIBPDU Status[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.5.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.5.[{#SNMPINDEX}]1h2w0DISABLEDTEXTThe Status of inlet.PWT_1phase_MIBAmps[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.[{#SNMPINDEX}]1h2w0DISABLEDFLOATAThe phase1 current of inlet.PWT_1phase_MIBMULTIPLIER0.01{last()}>13{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 13ADISABLEDHIGHThe PDU is currently using more than 13 Amps.{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 16A{Powertek 1 Phase PDU:.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.[{#SNMPINDEX}].last()}>16{last()}>16{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 16ADISABLEDDISASTERThe PDU is currently using more than 16 Amps.PDU Inlet Voltage[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9.[{#SNMPINDEX}]1h2w0DISABLEDFLOATVThe phase1 voltage of inlet.PWT_1phase_MIBSupposedly the Power Factor of the PDU[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.12.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.12.[{#SNMPINDEX}]1h2w0DISABLEDFLOAT%The phase1 power factor of inlet.PWT_1phase_MIBMULTIPLIER0.1Voltage[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.[{#SNMPINDEX}]1h2w0DISABLEDFLOATVThe phase1 power of inlet.PWT_1phase_MIBMULTIPLIER0.1{last()}>245{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 245VDISABLEDHIGHThe voltage of the PDU is currently more than 245V, which is too high.{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 250V{Powertek 1 Phase PDU:.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.[{#SNMPINDEX}].last()}>250{last()}>250{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 250VDISABLEDDISASTERThe voltage of the PDU is currently more than 250V, which is too high.PDU Power Factor ?[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.[{#SNMPINDEX}]1h2w0DISABLEDFLOAT%The phase1 status of inlet.PWT_1phase_MIBSPSv1-MIB::inletStatusPhase1MULTIPLIER0.1{last()}<90{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 90%DISABLEDDISASTERThe power factor of the PDU is currently less than 90% which indicates power is leaking and not being used.{last()}<95{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 95%DISABLEDHIGHThe power factor of the PDU is currently less than 95% which indicates power is leaking and not being used.{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 90%{Powertek 1 Phase PDU:.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.[{#SNMPINDEX}].last()}<90SPSv1-MIB::pduPwrMonitoringInletCfgTableSNMP_AGENTdiscovery[{#TRAPSRECEIVERADDR},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2,{#RECEIVEREVENTLEVEL},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3,{#RECEIVERSNMPVER},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4,{#RECEIVERDESCRIPTION},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5,{#INLETCFGLOADCRITICAL},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2,{#INLETCFGLOADWARNING},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3,{#INLETCFGCURRCRITPHASE1},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4,{#INLETCFGCURRCRITPHASE2},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5].1.3.6.1.4.1.42610.1.4.4.1.6.1.33600DISABLEDA list to configure thresholds of inlet.SPSv1-MIB::inletCfgLoadCritical[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2.[{#SNMPINDEX}]1h2w0FLOATThe Critical Threshold of inlet load.PWT_1phase_MIBSPSv1-MIB::inletCfgLoadWarning[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3.[{#SNMPINDEX}]1h2w0FLOATThe Warning Threshold of inlet load.PWT_1phase_MIBSPSv1-MIB::inletCfgCurrCritPhase1[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4.[{#SNMPINDEX}]1h2w0FLOATThe Critical Threshold of pahse1 current of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgCurrCritPhase2[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5.[{#SNMPINDEX}]1h2w0FLOATThe Critical Threshold of pahse2 current of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgCurrCritPhase3[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.6.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.6.[{#SNMPINDEX}]1h2w0FLOATThe Critical Threshold of pahse3 current of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgCurrWarnPhase1[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.7.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.7.[{#SNMPINDEX}]1h2w0FLOATThe Warning Threshold of pahse1 current of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgCurrWarnPhase2[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.8.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.8.[{#SNMPINDEX}]1h2w0FLOATThe Warning Threshold of pahse2 current of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgCurrWarnPhase3[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.9.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.9.[{#SNMPINDEX}]1h2w0FLOATThe Warning Threshold of pahse3 current of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgVoltCritPhase1[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.10.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.10.[{#SNMPINDEX}]1h2w0FLOATThe Critical Threshold of pahse1 voltage of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgVoltCritPhase2[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.11.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.11.[{#SNMPINDEX}]1h2w0FLOATThe Critical Threshold of pahse2 voltage of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgVoltCritPhase3[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.12.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.12.[{#SNMPINDEX}]1h2w0FLOATThe Critical Threshold of pahse3 voltage of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgVoltWarnPhase1[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.13.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.13.[{#SNMPINDEX}]1h2w0FLOATThe Warning Threshold of pahse1 voltage of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgVoltWarnPhase2[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.14.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.14.[{#SNMPINDEX}]1h2w0FLOATThe Warning Threshold of pahse2 voltage of inlet.PWT_1phase_MIBSPSv1-MIB::inletCfgVoltWarnPhase3[{#SNMPINDEX}]SNMP_AGENT.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.15.{#SNMPINDEX}.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.15.[{#SNMPINDEX}]1h2w0FLOATThe Warning Threshold of pahse3 voltage of inlet.PWT_1phase_MIB{$SNMP_PORT}161All graphs220AmpsPowertek 1 Phase PDU90020000110000030Current Power UsagePowertek 1 Phase PDU90020010110000030Power and AmpsPowertek 1 Phase PDU90020001110000030VoltagePowertek 1 Phase PDU9002001111000003Amps20FIXEDFIXEDGRADIENT_LINE1A7C11- Powertek 1 Phase PDU.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1
Current Power Usage6000FIXEDFIXEDGRADIENT_LINE1A7C11- Powertek 1 Phase PDU.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1
Power and AmpsFIXEDGRADIENT_LINE1A7C11- Powertek 1 Phase PDU.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1
1GRADIENT_LINEF63100RIGHT- Powertek 1 Phase PDU.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1
Voltage220260FIXEDFIXEDGRADIENT_LINE1A7C11- Powertek 1 Phase PDU.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1
SPSv1-MIB::inletStatusPhase11normal2warning3criticalSPSv1-MIB::mailRecvEmailType1none2events3status4bothSPSv1-MIB::mailRecvEventLevel1critical2warning3informationalSPSv1-MIB::receiverEventLevel1critical2warning3informationalSPSv1-MIB::receiverSnmpVer1v12v23v3