zabbix_export: version: '6.0' date: '2021-11-21T22:07:12Z' groups: - uuid: 7df96b18c230490a9a0a9e2307226338 name: Templates templates: - uuid: 3ba3d38469a14d28b39265a4eef3c94a template: 'Powertek 1 Phase PDU' name: 'Powertek 1 Phase PDU' description: | ## Description Created by Joakim Kingström at Sports Interactive. ## Overview This template is for Powertek 1-phase PDU's. It consists of 25 Items, nine triggers, and four graphs. It also has four discovery rules, with one of them having nine trigger prototypes. The discovery rules are disabled by default since they only created noise for me, but might be useful for other people. ## Author Joakim Kingström groups: - name: Templates items: - uuid: 6623a2e5c47d458eae4ee2b1e600e652 name: 'Software version' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.1.1.0 key: .1.3.6.1.4.1.42610.1.4.4.1.1.1.0 delay: 1h trends: '0' value_type: TEXT description: 'The firmware version of the device.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 91f93234864f4f648e4de91536d9ff9f name: 'Serial number' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.1.2.0 key: .1.3.6.1.4.1.42610.1.4.4.1.1.2.0 delay: 1h trends: '0' value_type: TEXT description: 'A Model of this device.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 454bc60cbd114faa971c2f80418d0c28 name: 'IP Address' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.1.0 key: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.1.0 delay: 1h trends: '0' value_type: TEXT description: 'The ip address that NMS can identify the managed device.' tags: - tag: Application value: PWT_1phase_MIB - uuid: ccd749de0a1f4456b315f19ad2631578 name: Gateway type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.2.0 key: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.2.0 delay: 1h trends: '0' value_type: TEXT description: 'The default gateway that allow device managed through routers.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 781c48ed61a1454aa9eaacf0278d954d name: 'IPv4 Subnet' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.3.0 key: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.3.0 delay: 1h trends: '0' value_type: TEXT description: 'Internet address subnet mask' tags: - tag: Application value: PWT_1phase_MIB - uuid: f2eb9b68ee524d07b0a9a58784b34b4f name: 'Primary DNS' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.4.0 key: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.4.0 delay: 1h trends: '0' value_type: TEXT description: 'Internet address of Primary DNS Server' tags: - tag: Application value: PWT_1phase_MIB - uuid: 692b88a1254a4782bc67c892f945fcd7 name: 'Secondary DNS' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.5.0 key: .1.3.6.1.4.1.42610.1.4.4.1.2.1.2.5.0 delay: 1h trends: '0' value_type: TEXT description: 'Internet address of Secondary DNS' tags: - tag: Application value: PWT_1phase_MIB - uuid: e894916d629747b0b6a328bbe558b15b name: 'System Name' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.3.1.0 key: .1.3.6.1.4.1.42610.1.4.4.1.3.1.0 delay: 1h trends: '0' value_type: TEXT description: 'The name of system.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 0d3ff482bda24962b4e8f71bf5319176 name: 'System Contact' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.3.2.0 key: .1.3.6.1.4.1.42610.1.4.4.1.3.2.0 delay: 1h trends: '0' value_type: TEXT description: 'The contact of system.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 300cbb6fb5d3458ca1234364a7f4a3c8 name: 'System Location' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.3.3.0 key: .1.3.6.1.4.1.42610.1.4.4.1.3.3.0 delay: 1h trends: '0' value_type: TEXT description: 'The location of system.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 83d11e3293514499b4c444bc41f477d5 name: 'System Time' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.3.6.1.0 key: .1.3.6.1.4.1.42610.1.4.4.1.3.6.1.0 delay: 1h trends: '0' value_type: TEXT description: 'The date/time in agent' tags: - tag: Application value: PWT_1phase_MIB - uuid: 45cb15b7fba6455d9ab0eb29f1266b36 name: 'NTP Server' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.3.6.7.2.0 key: .1.3.6.1.4.1.42610.1.4.4.1.3.6.7.2.0 delay: 1h trends: '0' value_type: TEXT description: 'The ip address of NTP server.' tags: - tag: Application value: PWT_1phase_MIB - uuid: ddeddf05ad0c4846a963e457504c922d name: 'SNMP Port' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.4.2.0 key: .1.3.6.1.4.1.42610.1.4.4.1.4.2.0 delay: 1h value_type: FLOAT description: 'The UDP port for SNMP.' tags: - tag: Application value: PWT_1phase_MIB - uuid: a2d9dcd8aaf444e9a9af368c2b62686e name: 'SNMP version' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.4.3.0 key: .1.3.6.1.4.1.42610.1.4.4.1.4.3.0 delay: 1h value_type: FLOAT description: 'Set SNMP version.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 24e8242666dc4cc980e59573d79422ef name: 'SMTP Server' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.5.1.0 key: .1.3.6.1.4.1.42610.1.4.4.1.5.1.0 delay: 1h trends: '0' value_type: TEXT description: 'The address of Email server.' tags: - tag: Application value: PWT_1phase_MIB - uuid: d2905689f1b54e16ad5007424e08b675 name: 'SMTP Port' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.5.2.0 key: .1.3.6.1.4.1.42610.1.4.4.1.5.2.0 delay: 1h value_type: FLOAT description: 'The UDP port for Email Server.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 0e1f71c21431407ca6cd152e684e91b1 name: 'Email sender address' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.5.3.0 key: .1.3.6.1.4.1.42610.1.4.4.1.5.3.0 delay: 1h trends: '0' value_type: TEXT description: 'The sender\''s Email address' tags: - tag: Application value: PWT_1phase_MIB - uuid: fe8c41ca63cc417ab99758d2e5520d9f name: 'Email Prefix' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.5.4.0 key: .1.3.6.1.4.1.42610.1.4.4.1.5.4.0 delay: 1h trends: '0' value_type: TEXT description: 'The prefix string of mail subject' tags: - tag: Application value: PWT_1phase_MIB - uuid: 11aeefadf45e4af4ab67be3314f9015e name: 'Active Power' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1 key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1 value_type: FLOAT units: W description: 'The power that the PDU is currently using.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: PWT_1phase_MIB triggers: - uuid: 93652901ad944c2cb7e31c9ed147f0fd expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1)>4600' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 4.6 kW' priority: HIGH description: 'The power used currently is more than 4.6 kW.' dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 5.8 kW' expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1)>5800' - uuid: ae53e8c1ae304829a23052801bbd6104 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1)>5800' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 5.8 kW' priority: DISASTER description: 'The power used currently is more than 5.8 kW.' - uuid: 4601dbedd1ac40239863fa8c491937ea name: 'PDU Reset Date' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.1 key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.1 delay: 10m trends: '0' value_type: TEXT description: 'The reset date of the PDU.' tags: - tag: Application value: PWT_1phase_MIB triggers: - uuid: eddd50f0cadd41789c655b82dd85f756 expression: '(last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.1,#1)<>last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.1,#2))=1' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: PDU Reset Date changed' priority: WARNING description: 'The PDU reset has changed, indicating that the PDU has been switched off and on.' - uuid: 5585133581104c3492ab22f19981f5cf name: 'Energy used' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4.1 key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4.1 delay: 1h value_type: FLOAT units: W description: 'The total energy used by the PDU.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 25a4c8d4d651453095713706a9c06ec6 name: Amps type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1 key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1 value_type: FLOAT units: A description: 'The amps currently used by the PDU.' preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: PWT_1phase_MIB triggers: - uuid: 796523b52c3a4a2ab236fb33c7270a79 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1)>13' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 13A' priority: HIGH description: 'The PDU is currently using more than 13 Amps.' dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 16A' expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1)>16' - uuid: b324bd3cfaef465b8157a415fbd58030 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1)>16' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 16A' priority: DISASTER description: 'The PDU is currently using more than 16 Amps.' - uuid: 3952b182e3cf436ea9d80969867aa268 name: 'PDU Inlet Voltage' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9.1 key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9.1 value_type: FLOAT units: V description: 'The current voltage of the PDU.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 7f28b7f67c364254a13c1acd8795bed9 name: Voltage type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1 key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1 value_type: FLOAT units: V description: 'The Voltage of the PDU.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: PWT_1phase_MIB triggers: - uuid: f6188e68dc474b1db4ec5a4513bf03a3 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1)>245' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 245V' priority: HIGH description: 'The voltage of the PDU is currently more than 245V, which is too high.' dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 250V' expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1)>250' - uuid: 9619a54a2514483caeb980abc50ad550 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1)>250' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 250V' priority: DISASTER description: 'The voltage of the PDU is currently more than 250V, which is too high.' - uuid: b3ac78812129418eb1e1ba3644ef55b5 name: 'PDU Power Factor' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.1 key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.1 delay: 1h status: DISABLED value_type: FLOAT units: '%' description: 'The power factor of the PDU indicates how much of the power is actually used.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: PWT_1phase_MIB triggers: - uuid: 5aaf878104b84a47bbd853692676c4f9 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.1)<90' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 90%' priority: DISASTER description: 'The power factor of the PDU is currently less than 90% which indicates power is leaking and not being used.' - uuid: 9f1b1f78c23d4c9e861deadecb6c9189 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.1)<95' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 95%' priority: HIGH description: 'The power factor of the PDU is currently less than 95% which indicates power is leaking and not being used.' dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 90%' expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.1)<90' discovery_rules: - uuid: 5b7e00ae22164a86af0d47737a9e1015 name: 'SPSv1-MIB::pduSnmpTrapsReceiversTable' type: SNMP_AGENT snmp_oid: 'discovery[{#TRAPSRECEIVERADDR},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2,{#RECEIVEREVENTLEVEL},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3,{#RECEIVERSNMPVER},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4,{#RECEIVERDESCRIPTION},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5]' key: .1.3.6.1.4.1.42610.1.4.4.1.4.4 delay: '3600' status: DISABLED description: "A list of managers to send traps to. The number of\r entries is given by the value of pduSnmpNumTrapReceivers" item_prototypes: - uuid: 7b0d6a0f40de4bf09160918cd1f1a317 name: 'SPSv1-MIB::trapsReceiverAddr[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: TEXT description: 'The IP address of the manager to send a trap to.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 6134c6dd162748f8a10d1a953bae33a6 name: 'SPSv1-MIB::receiverEventLevel[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The severity level of traps to be received by this manager.' valuemap: name: 'SPSv1-MIB::receiverEventLevel' tags: - tag: Application value: PWT_1phase_MIB - uuid: 4918b6f3c5a645de887225ae327fb4e3 name: 'SPSv1-MIB::receiverSnmpVer[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The SNMP Trap version of trap receivers.' valuemap: name: 'SPSv1-MIB::receiverSnmpVer' tags: - tag: Application value: PWT_1phase_MIB - uuid: 1fd5fff434134eadae484413f3cf18ff name: 'SPSv1-MIB::receiverDescription[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: TEXT description: 'Description of trap receivers' tags: - tag: Application value: PWT_1phase_MIB - uuid: a4b72b2e673a422c90f2eb7fb1787524 name: 'SPSv1-MIB::pduEmailReceiversTable' type: SNMP_AGENT snmp_oid: 'discovery[{#TRAPSRECEIVERADDR},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2,{#RECEIVEREVENTLEVEL},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3,{#RECEIVERSNMPVER},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4,{#RECEIVERDESCRIPTION},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5,{#INLETCFGLOADCRITICAL},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2,{#INLETCFGLOADWARNING},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3,{#INLETCFGCURRCRITPHASE1},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4,{#INLETCFGCURRCRITPHASE2},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5]' key: .1.3.6.1.4.1.42610.1.4.4.1.5.8 delay: '3600' status: DISABLED description: 'A list of managers to send email notification to.' item_prototypes: - uuid: 84dc3abcd54648d4b9a9ab72a776b8d2 name: 'SPSv1-MIB::mailRecvReceiverAddr[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.2.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.2.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: TEXT description: 'The Email address of the manager to send a email notification to.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 6b3cde228730443fa1f5a9907434b203 name: 'SPSv1-MIB::mailRecvEmailType[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.3.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.3.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Email Type of email notification receivers.' valuemap: name: 'SPSv1-MIB::mailRecvEmailType' tags: - tag: Application value: PWT_1phase_MIB - uuid: bd6ad0ae80bf42ee9a73be6a098731bf name: 'SPSv1-MIB::mailRecvEventLevel[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.4.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.4.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The severity level of email notification to be received by this manager.' valuemap: name: 'SPSv1-MIB::mailRecvEventLevel' tags: - tag: Application value: PWT_1phase_MIB - uuid: e30bc8d19d7d4f5ebe8f6376e78c7c38 name: 'SPSv1-MIB::mailRecvDescription[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.5.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.5.8.1.5.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: TEXT description: 'Description of email notification receivers' tags: - tag: Application value: PWT_1phase_MIB - uuid: e1388e4f22d94d88b20aea0ea61caa46 name: 'SPSv1-MIB::pduPwrMonitoringInletStatusTable' type: SNMP_AGENT snmp_oid: 'discovery[{#TRAPSRECEIVERADDR},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2,{#RECEIVEREVENTLEVEL},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3,{#RECEIVERSNMPVER},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4,{#RECEIVERDESCRIPTION},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5,{#INLETCFGLOADCRITICAL},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2,{#INLETCFGLOADWARNING},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3,{#INLETCFGCURRCRITPHASE1},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4,{#INLETCFGCURRCRITPHASE2},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5]' key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2 delay: '3600' status: DISABLED description: 'A list to display status of Inlet.' item_prototypes: - uuid: 1b7768e977af4526ac3d12858491e9ab name: 'Active Power[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: FLOAT units: W description: 'The total power of inlet.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: PWT_1phase_MIB trigger_prototypes: - uuid: 8bbac27432f9473cae3b13f832a31c99 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.[{#SNMPINDEX}])>4.6' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 4.6 kW' status: DISABLED priority: HIGH description: 'The power used currently is more than 4.6 kW.' dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 5.8 kW' expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.[{#SNMPINDEX}])>5.8' - uuid: fce7d30c32a84d389d6d21826ba541ae expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.[{#SNMPINDEX}])>5.8' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Active Power > 5.8 kW' status: DISABLED priority: DISASTER description: 'The power used currently is more than 5.8 kW.' - uuid: 3dd3b90cc9bd4867847f1789ae23cfae name: 'PDU Reset Date[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: TEXT description: 'The reset date of inlet.' tags: - tag: Application value: PWT_1phase_MIB trigger_prototypes: - uuid: 300748f715e7457a9b1d5b47a76ef23d expression: '(last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.[{#SNMPINDEX}],#1)<>last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3.[{#SNMPINDEX}],#2))=1' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: PDU Reset Date changed' status: DISABLED priority: WARNING description: 'The PDU reset has changed, indicating that the PDU has been switched off and on.' - uuid: 82fdc49e0e30470da9c5ed264e9ce2c2 name: 'Energy used[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: FLOAT units: W description: 'The total energy of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 684b941a6e5944338d3542cae49efa61 name: 'PDU Status[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.5.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.5.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: TEXT description: 'The Status of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 7d2a98e2de7147119450b85fe5bc70af name: 'Amps[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: FLOAT units: A description: 'The phase1 current of inlet.' preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: PWT_1phase_MIB trigger_prototypes: - uuid: 9471381b7f154636bdca0590ff87347a expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.[{#SNMPINDEX}])>13' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 13A' status: DISABLED priority: HIGH description: 'The PDU is currently using more than 13 Amps.' dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 16A' expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.[{#SNMPINDEX}])>16' - uuid: f0b84b67c4a24c839653be6354045720 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.[{#SNMPINDEX}])>16' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Amps > 16A' status: DISABLED priority: DISASTER description: 'The PDU is currently using more than 16 Amps.' - uuid: 08918cb169cb4f11896bfcd26b5e7562 name: 'PDU Inlet Voltage[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: FLOAT units: V description: 'The phase1 voltage of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 6f5f819cb6284743a76f5d9a1b257784 name: 'Supposedly the Power Factor of the PDU[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.12.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.12.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: FLOAT units: '%' description: 'The phase1 power factor of inlet.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: PWT_1phase_MIB - uuid: 10b556c14880444f996cfd7f4967f09c name: 'Voltage[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: FLOAT units: V description: 'The phase1 power of inlet.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: PWT_1phase_MIB trigger_prototypes: - uuid: 88ff2da1cd38481993ff1a9cc05a2637 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.[{#SNMPINDEX}])>245' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 245V' status: DISABLED priority: HIGH description: 'The voltage of the PDU is currently more than 245V, which is too high.' dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 250V' expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.[{#SNMPINDEX}])>250' - uuid: 3fa8143f28c54eefaeeef3dfed34c77e expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.[{#SNMPINDEX}])>250' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Voltage > 250V' status: DISABLED priority: DISASTER description: 'The voltage of the PDU is currently more than 250V, which is too high.' - uuid: 862a838736a3496a901d6bdd6ad9eb30 name: 'PDU Power Factor ?[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' status: DISABLED value_type: FLOAT units: '%' description: 'The phase1 status of inlet.' valuemap: name: 'SPSv1-MIB::inletStatusPhase1' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: PWT_1phase_MIB trigger_prototypes: - uuid: 6b5eec3612a74f45a98342d4332270f3 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.[{#SNMPINDEX}])<90' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 90%' status: DISABLED priority: DISASTER description: 'The power factor of the PDU is currently less than 90% which indicates power is leaking and not being used.' - uuid: 1342dc1f902741a3abda257b51885971 expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.[{#SNMPINDEX}])<95' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 95%' status: DISABLED priority: HIGH description: 'The power factor of the PDU is currently less than 95% which indicates power is leaking and not being used.' dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Power Factor < 90%' expression: 'last(/Powertek 1 Phase PDU/.1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18.[{#SNMPINDEX}])<90' - uuid: c38e0c67d11749b089e3c978115939d8 name: 'SPSv1-MIB::pduPwrMonitoringInletCfgTable' type: SNMP_AGENT snmp_oid: 'discovery[{#TRAPSRECEIVERADDR},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2,{#RECEIVEREVENTLEVEL},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3,{#RECEIVERSNMPVER},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4,{#RECEIVERDESCRIPTION},.1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5,{#INLETCFGLOADCRITICAL},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2,{#INLETCFGLOADWARNING},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3,{#INLETCFGCURRCRITPHASE1},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4,{#INLETCFGCURRCRITPHASE2},.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5]' key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.3 delay: '3600' status: DISABLED description: 'A list to configure thresholds of inlet.' item_prototypes: - uuid: d66aa5a309ef48e0b347eb5f4ae0d37e name: 'SPSv1-MIB::inletCfgLoadCritical[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Critical Threshold of inlet load.' tags: - tag: Application value: PWT_1phase_MIB - uuid: f4e5953ed02c4a8f9d0d975e72da12d3 name: 'SPSv1-MIB::inletCfgLoadWarning[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Warning Threshold of inlet load.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 1e2a9ce61551416ea98eed56a94d861b name: 'SPSv1-MIB::inletCfgCurrCritPhase1[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Critical Threshold of pahse1 current of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 355cb11e935d46bf9ce327b3067134cc name: 'SPSv1-MIB::inletCfgCurrCritPhase2[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Critical Threshold of pahse2 current of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 6c30f85167b5468abf6c54e4533983af name: 'SPSv1-MIB::inletCfgCurrCritPhase3[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.6.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.6.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Critical Threshold of pahse3 current of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 7ffe95b6351041ba990d53a11d2e6df3 name: 'SPSv1-MIB::inletCfgCurrWarnPhase1[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.7.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.7.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Warning Threshold of pahse1 current of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: ae48537ee32144e99efa2e6faef5da2a name: 'SPSv1-MIB::inletCfgCurrWarnPhase2[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.8.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.8.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Warning Threshold of pahse2 current of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 170f9f7025dc47d29926b0c05d8653a1 name: 'SPSv1-MIB::inletCfgCurrWarnPhase3[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.9.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.9.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Warning Threshold of pahse3 current of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 21c1f882a6054793adb50b21a157dc7a name: 'SPSv1-MIB::inletCfgVoltCritPhase1[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.10.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.10.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Critical Threshold of pahse1 voltage of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 35adc797547447cb951a66a385ae5f7b name: 'SPSv1-MIB::inletCfgVoltCritPhase2[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.11.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.11.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Critical Threshold of pahse2 voltage of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: a0ff09a5714e4a7db2e2aa7067ff0e5f name: 'SPSv1-MIB::inletCfgVoltCritPhase3[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.12.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.12.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Critical Threshold of pahse3 voltage of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 82ef0c19f2f643a48874bec2c4bbbbbc name: 'SPSv1-MIB::inletCfgVoltWarnPhase1[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.13.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.13.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Warning Threshold of pahse1 voltage of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: f4f288de478a450bbe6d194a12d18118 name: 'SPSv1-MIB::inletCfgVoltWarnPhase2[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.14.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.14.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Warning Threshold of pahse2 voltage of inlet.' tags: - tag: Application value: PWT_1phase_MIB - uuid: 9e359cdaf84d46c693f37b13eb1e5b0d name: 'SPSv1-MIB::inletCfgVoltWarnPhase3[{#SNMPINDEX}]' type: SNMP_AGENT snmp_oid: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.15.{#SNMPINDEX}' key: '.1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.15.[{#SNMPINDEX}]' delay: 1h history: 2w trends: '0' value_type: FLOAT description: 'The Warning Threshold of pahse3 voltage of inlet.' tags: - tag: Application value: PWT_1phase_MIB macros: - macro: '{$SNMP_PORT}' value: '161' dashboards: - uuid: a7a1f7d43ac24900807d598dcf9bf307 name: 'All graphs' pages: - widgets: - type: GRAPH_CLASSIC width: '12' height: '6' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Amps host: 'Powertek 1 Phase PDU' - type: GRAPH_CLASSIC x: '12' width: '12' height: '6' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'Current Power Usage' host: 'Powertek 1 Phase PDU' - type: GRAPH_CLASSIC 'y': '6' width: '12' height: '6' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'Power and Amps' host: 'Powertek 1 Phase PDU' - type: GRAPH_CLASSIC x: '12' 'y': '6' width: '12' height: '6' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: Voltage host: 'Powertek 1 Phase PDU' valuemaps: - uuid: 58ea58b6f29e41989c9d1374cfab5cf6 name: 'SPSv1-MIB::inletStatusPhase1' mappings: - value: '1' newvalue: normal - value: '2' newvalue: warning - value: '3' newvalue: critical - uuid: 1439ec4e54484b1c94bde5d0e6000765 name: 'SPSv1-MIB::mailRecvEmailType' mappings: - value: '1' newvalue: none - value: '2' newvalue: events - value: '3' newvalue: status - value: '4' newvalue: both - uuid: 3b9011a26c6049dfb928a688148b3ebe name: 'SPSv1-MIB::mailRecvEventLevel' mappings: - value: '1' newvalue: critical - value: '2' newvalue: warning - value: '3' newvalue: informational - uuid: c15b8af8371f4fd1a58285d7d23e210c name: 'SPSv1-MIB::receiverEventLevel' mappings: - value: '1' newvalue: critical - value: '2' newvalue: warning - value: '3' newvalue: informational - uuid: 62ec25215db14acaab5dd38621296184 name: 'SPSv1-MIB::receiverSnmpVer' mappings: - value: '1' newvalue: v1 - value: '2' newvalue: v2 - value: '3' newvalue: v3 graphs: - uuid: 375d6b977d864a4d9be68d9218651a10 name: Amps yaxismax: '20' ymin_type_1: FIXED ymax_type_1: FIXED graph_items: - drawtype: GRADIENT_LINE color: 1A7C11 item: host: 'Powertek 1 Phase PDU' key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1 - uuid: 69a453fe333a4c0c862f6dfc159c4172 name: 'Current Power Usage' yaxismax: '6000' ymin_type_1: FIXED ymax_type_1: FIXED graph_items: - drawtype: GRADIENT_LINE color: 1A7C11 item: host: 'Powertek 1 Phase PDU' key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1 - uuid: e80e8358ca18491f93f359c17c11c5a6 name: 'Power and Amps' ymin_type_1: FIXED graph_items: - drawtype: GRADIENT_LINE color: 1A7C11 item: host: 'Powertek 1 Phase PDU' key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2.1 - sortorder: '1' drawtype: GRADIENT_LINE color: F63100 yaxisside: RIGHT item: host: 'Powertek 1 Phase PDU' key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6.1 - uuid: 4c383eb07e6e4353a6f99e9036eaaf81 name: Voltage yaxismin: '220' yaxismax: '260' ymin_type_1: FIXED ymax_type_1: FIXED graph_items: - drawtype: GRADIENT_LINE color: 1A7C11 item: host: 'Powertek 1 Phase PDU' key: .1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15.1