5.02021-11-21T21:56:22ZTemplates/RPPSNMP Riello UPSSNMP Riello UPS## Overview
Basic Riello UPS Template no MIBs needed
## Author
I. Aliaga U.
Templates/RPPBateryBypass LinesGeneralInput LinesOutput LinesSNMP agentUPS Status- Battery CurrentSNMP_AGENT.1.3.6.1.4.1.5491.10.1.2.6.0rupsBatteryCurrent.060s30d60dABateryMULTIPLIER0.1
- Battery StatusSNMP_AGENT.1.3.6.1.4.1.5491.10.1.2.1.0rupsBatteryStatus.060s30d60dBateryupsBatteryStatus
- Battery TemperatureSNMP_AGENT.1.3.6.1.4.1.5491.10.1.2.7.0rupsBatteryTemperature.060s30d60dºCBatery{min(300)}>45Temperature of batteries above 45ºCWARNINGPOWER{min(300)}>55Temperature of batteries above 55ºCHIGHAll batteries have a rated capacity which is determined based on specified conditions. The rated capacity of a UPS battery is based on an ambient temperature of 25°C (77°F). Operating the UPS under these conditions will maximize the life of the UPS and result in optimal performance. While a UPS will continue to operate in varying temperatures, it is important to note that this will likely result in diminishing the performance and lifespan of your battery. A general rule to remember is that for every 8.3°C (15°F) above the ambient temperature of 25°C (77°F), the life of the battery will be reduced by 50 percent. Therefore, keeping a UPS at a comfortable temperature is crucial to maximizing UPS life and capabilities.POWER{max(300)}<15Temperature of batteries below 15ºCAVERAGEUnder 19º battery capacity will get reduced although life will be extendedPOWER
- Battery VoltageSNMP_AGENT.1.3.6.1.4.1.5491.10.1.2.5.0rupsBatteryVoltage.060s30d60dVBateryMULTIPLIER0.1{max(#2)}<({$NOMINAL_VOLTAGE}*0.9)Battery voltage under {$NOMINAL_VOLTAGE}HIGHPOWER
- Bypass frequencySNMP_AGENT.1.3.6.1.4.1.5491.10.1.5.1.0rupsBypassFrequency.060s30d60dHzBypass LinesMULTIPLIER0.1{min(#2)}>{$NOMINAL_FREQUENCY}+1 or {max(#2)}<{$NOMINAL_FREQUENCY}-1Bypass frecuency is not {$NOMINAL_FREQUENCY}HIGHPOWER
- Estimated Charge RemainingSNMP_AGENT.1.3.6.1.4.1.5491.10.1.2.4.0rupsEstimatedChargeRemaining.060s30d60d%UPS Status{change()}>0 and {last()}<100Batteries are chargingINFOPOWER{change()}<0 and {last()}>0Batteries are dischargingWARNINGPOWER
- Estimated Minutes RemainingSNMP_AGENT.1.3.6.1.4.1.5491.10.1.2.3.0rupsEstimatedMinutesRemaining.060s30d60dminutesUPS Status{max(#2)}<5Estimated battery minutes remaining < 5AVERAGEPOWER
- Ups Agent VersionSNMP_AGENT.1.3.6.1.4.1.5491.10.1.1.4.0rupsIdentAgentSoftwareVersion.01d30d0CHARSOFTWAREGeneral
- Model nameSNMP_AGENT.1.3.6.1.4.1.5491.10.1.1.2.0rupsIdentModel.01d30d0CHARMODELGeneral
- Software versionSNMP_AGENT.1.3.6.1.4.1.5491.10.1.1.3.0rupsIdentUPSSoftwareVersion.01d30d0CHAROSGeneral
- Input Line BadsSNMP_AGENT.1.3.6.1.4.1.5491.10.1.3.1.0rupsInputLineBads.060s30d60dInput Lines{change()}>0Input Line Bads detectedWARNINGPOWER
- Output frequencySNMP_AGENT.1.3.6.1.4.1.5491.10.1.4.2.0rupsOutputFrequency.060s30d60dFLOATHzOutput LinesMULTIPLIER0.1{min(#2)}>{$NOMINAL_FREQUENCY}+1 or {max(#2)}<{$NOMINAL_FREQUENCY}-1Output frecuency is not {$NOMINAL_FREQUENCY}HIGHPOWER
- Output sourceSNMP_AGENT.1.3.6.1.4.1.5491.10.1.4.1.0rupsOutputSource.060s30d60dOutput LinesupsOutputSource{last()}<>3 and {prev()}<>3Output source has changed!DISABLEDAVERAGEPOWER
- Seconds on BatterySNMP_AGENT.1.3.6.1.4.1.5491.10.1.2.2.0rupsSecondsOnBattery.060s30d60dsecondsUPS Status
- System TemperatureSNMP_AGENT.1.3.6.1.4.1.5491.10.1.10.1.0rupsSystemTemperature.030s°CUPS Status
- Alarms PresentSNMP_AGENT.1.3.6.1.4.1.5491.10.1.6.1.0upsAlarmsPresent.060s30d60dalarmsUPS Status{last()}>0Alarm present!HIGHPOWER
- Agent availabilityINTERNALzabbix[host,snmp,available]30s7dThe agent always returns 1 for this item. It could be used in combination with nodata() for availability check.SNMP agentHost availability
Bypass LinesSNMP_AGENTdiscovery[{#BYPASSV},.1.3.6.1.4.1.5491.10.1.5.3.1.2]BypassLinesD30sLine {#SNMPINDEX} Bypass CurrentSNMP_AGENT.1.3.6.1.4.1.5491.10.1.5.3.1.3.{#SNMPINDEX}rupsBypassCurrent[{#SNMPINDEX}]30sFLOATABypass LinesMULTIPLIER.1Line {#SNMPINDEX} Bypass PowerSNMP_AGENT.1.3.6.1.4.1.5491.10.1.5.3.1.4.{#SNMPINDEX}rupsBypassPower[{#SNMPINDEX}]30swBypass LinesLine {#SNMPINDEX} Bypass VoltageSNMP_AGENT.1.3.6.1.4.1.5491.10.1.5.3.1.2.{#SNMPINDEX}rupsBypassVoltage[{#SNMPINDEX}]30sVBypass LinesInput LinesSNMP_AGENTdiscovery[{#INPUTF},.1.3.6.1.4.1.5491.10.1.3.3.1.2]InputLinesD30sLine {#SNMPINDEX} Input CurrentSNMP_AGENT.1.3.6.1.4.1.5491.10.1.3.3.1.4.{#SNMPINDEX}rupsInputCurrent.[{#SNMPINDEX}]30sFLOATAInput LinesMULTIPLIER.1Line {#SNMPINDEX} Input FrequencySNMP_AGENT.1.3.6.1.4.1.5491.10.1.3.3.1.2.{#SNMPINDEX}rupsInputFrequency.[{#SNMPINDEX}]30sFLOATHzInput LinesMULTIPLIER.1Line {#SNMPINDEX} Input True PowerSNMP_AGENT.1.3.6.1.4.1.5491.10.1.3.3.1.5.{#SNMPINDEX}rupsInputTruePower.[{#SNMPINDEX}]30sWInput LinesLine {#SNMPINDEX} Input VoltageSNMP_AGENT.1.3.6.1.4.1.5491.10.1.3.3.1.3.{#SNMPINDEX}rupsInputVolage.[{#SNMPINDEX}]30sVInput Lines{max(#2)}<({$NOMINAL_VOLTAGE}*0.9)Bypass voltage on line {#SNMPINDEX} below {$NOMINAL_VOLTAGE}HIGHOutput LinesSNMP_AGENTdiscovery[{#OUTPUTV},.1.3.6.1.4.1.5491.10.1.4.4.1.2]OutputLinesD30sLine {#SNMPINDEX} Output CurrentSNMP_AGENT.1.3.6.1.4.1.5491.10.1.4.4.1.3.{#SNMPINDEX}rupsOutputCurrent.[{#SNMPINDEX}]30sFLOATAOutput LinesMULTIPLIER.1Line {#SNMPINDEX} Output Peak CurrentSNMP_AGENT.1.3.6.1.4.1.5491.10.1.4.4.1.6.{#SNMPINDEX}rupsOutputPeakCurrent.[{#SNMPINDEX}]30sFLOATAOutput LinesMULTIPLIER.1Line {#SNMPINDEX} Output % LoadSNMP_AGENT.1.3.6.1.4.1.5491.10.1.4.4.1.5.{#SNMPINDEX}rupsOutputPercetLoad.[{#SNMPINDEX}]30s%Output LinesLine {#SNMPINDEX} Output PowerSNMP_AGENT.1.3.6.1.4.1.5491.10.1.4.4.1.4.{#SNMPINDEX}rupsOutputPower.[{#SNMPINDEX}]30swOutput LinesLine {#SNMPINDEX} Output VoltageSNMP_AGENT.1.3.6.1.4.1.5491.10.1.4.4.1.2.{#SNMPINDEX}rupsOutputVoltage.[{#SNMPINDEX}]30sVOutput Lines{$NOMINAL_FREQUENCY}60{$NOMINAL_VOLTAGE}230Battery StatusBOLD_LINE1A7C11- SNMP Riello UPSrupsBatteryStatus.0
Battery TemperatureBOLD_LINE1A7C11- SNMP Riello UPSrupsBatteryTemperature.0
Host availability0not available1available2unknownupsBatteryStatus1Unknown2Normal3Low4DepletedupsOutputSource1Other2None3Normal4Bypass5Battery6Booster7Reducer