zabbix_export: version: '6.0' date: '2021-11-21T21:42:24Z' groups: - uuid: 7df96b18c230490a9a0a9e2307226338 name: Templates templates: - uuid: ee85c1cf3c0947b59384487a42d2d6ba template: Stark-3000-snmp name: Stark-3000-snmp description: | ## Overview UPS Stark country 3000 online. Template based on "Template\_UPS\_Inform-flexipower" ## Author Sergey Prisada groups: - name: Templates items: - uuid: 646dd0b868b04ecda076a17fc32212f2 name: 'Extend work temperature' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.3.13.0 key: iemStatusProbeCurrentTemp delay: '30' units: C description: 'The ambient temperature at or near the UPS Battery casing.' tags: - tag: Application value: Environmental triggers: - uuid: 1c688a2ebddf49bcabdec5408e8555b5 expression: 'avg(/Stark-3000-snmp/iemStatusProbeCurrentTemp,30s)>400' name: 'Ambient temperature critical' priority: HIGH - uuid: 94e4527572864bca9e658413bbd8bf26 expression: 'avg(/Stark-3000-snmp/iemStatusProbeCurrentTemp,30s)>300' name: 'Ambient temperature high' priority: WARNING - uuid: 85414efb0b8f4456bb5126f30f85e595 expression: 'avg(/Stark-3000-snmp/iemStatusProbeCurrentTemp,30s)<150' name: 'Ambient temperature too low' priority: AVERAGE - uuid: 98496ba7876a48c1a668af9382e8a319 name: 'Ups bat est charge remaining' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.3.1.0 key: oid.companymib.upsbattery.upsbatstatus delay: '30' units: '%' description: 'An estimate of the battery charge remaining expressed as a percent of full charge.' preprocessing: - type: MULTIPLIER parameters: - '0.01' tags: - tag: Application value: Battery - uuid: 3606c7646b0f4741a5db0247ef1f54f8 name: 'The present bypass frequency' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.6.1.0 key: PresentBypassFrequency delay: '30' units: Hz description: 'The present bypass frequency.' tags: - tag: Application value: Environmental - uuid: f5872ad0bfdc461db021fe36a30b0af3 name: 'Battery voltage' type: SNMP_AGENT snmp_oid: iso.3.6.1.2.1.33.1.2.5.0 key: upsAdvBatteryActualVoltage delay: '180' units: V tags: - tag: Application value: Battery - uuid: 53d02c223c1549f493ee961630d69513 name: 'Battery charge' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.3.4.0 key: upsAdvBatteryCapacity delay: '30' units: '%' description: 'An estimate of the battery charge remaining expressed as a percent of full charge.' tags: - tag: Application value: Battery triggers: - uuid: db5d0d187d014dff898d4580d087ff08 expression: last(/Stark-3000-snmp/upsAdvBatteryCapacity)<20 name: 'Battery charge critically low' priority: HIGH - uuid: d0a65202b5c34d38ae55095a833545e6 expression: last(/Stark-3000-snmp/upsAdvBatteryCapacity)<50 name: 'Battery charge low' priority: WARNING - uuid: 21a929d6cca544659fb6718556cbc898 name: 'Battery status' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.3.1.0 key: upsAdvBatteryReplaceIndicator delay: '180' description: 'The indication of the capacity remaining in the UPS system''s batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is mandatoryly absent and the UPS is unable to sustain the output). unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4), batteryDischarging(5), batteryFailure(6), batteryReplace(7), batterysilence(8)' valuemap: name: 'STARK Batary status' tags: - tag: Application value: Battery triggers: - uuid: 04c0e7fa509f40488572f88ac752fe28 expression: last(/Stark-3000-snmp/upsAdvBatteryReplaceIndicator)=4 name: 'Battery Depleted' priority: HIGH - uuid: 5ea0dcd7a8044956b7deb6e0eebb9c22 expression: last(/Stark-3000-snmp/upsAdvBatteryReplaceIndicator)=6 name: 'Battery Failure' priority: DISASTER - uuid: b4ed66e7f3824034bf821b030e2241b6 expression: last(/Stark-3000-snmp/upsAdvBatteryReplaceIndicator)=7 name: 'Battery Replace' priority: DISASTER - uuid: 6b28cc0bffbc452bba0483451392fa87 name: 'Input frequency' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.6.1.0 key: upsAdvInputFrequency delay: '180' units: Hz description: 'The present bypass frequency.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Power - uuid: a5dcfc8c39f54d24826c9306d0baa621 name: 'Input voltage' type: SNMP_AGENT snmp_oid: iso.3.6.1.4.1.21111.1.1.4.5.1.3.0 key: upsAdvInputLineVoltage delay: '30' units: V description: 'The input utility line voltage.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Power triggers: - uuid: 43dbf3cc882343f4bbcbe1a3630cc5d8 expression: 'avg(/Stark-3000-snmp/upsAdvInputLineVoltage,30s)<190' name: 'Input voltage low' priority: WARNING - uuid: 2a3dc96a675942ec97f3db1a01a6504c expression: 'avg(/Stark-3000-snmp/upsAdvInputLineVoltage,30s)>250' name: 'Input voltage too high' priority: WARNING - uuid: 7a39af12f9a04c309665e04dbc57ca76 expression: 'avg(/Stark-3000-snmp/upsAdvInputLineVoltage,30s)=0' name: 'No power input' priority: DISASTER description: 'Input voltage is zero' - uuid: 0d39299f798341149673253beeaf627a name: 'Load current in procent' type: SNMP_AGENT snmp_oid: iso.3.6.1.4.1.21111.1.1.5.7.1.7.0 key: upsAdvOutputCurrent delay: '30' units: '%' description: 'The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.' tags: - tag: Application value: Power triggers: - uuid: 64c7b3e5974e44b7878858c3aa309e6a expression: 'last(/Stark-3000-snmp/upsAdvOutputCurrent,#10)>=85' name: Overload priority: DISASTER - uuid: 1d278012d7c64cd680cd14191c37f716 name: 'Output frequency' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.5.2.0 key: upsAdvOutputFrequency delay: '180' units: Hz description: 'The current output frequency of the UPS system' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Power - uuid: e2e34f35651b4e978728cf1a2ead982f name: 'Output voltage' type: SNMP_AGENT snmp_oid: iso.3.6.1.4.1.21111.1.1.5.7.1.2.0 key: upsAdvOutputVoltage delay: '30' units: V description: 'The output voltage of the UPS system.' preprocessing: - type: MULTIPLIER parameters: - '0.1' tags: - tag: Application value: Power - uuid: f6f95d3b0fc14bbfae2f60f64495145a name: 'UPS model' type: SNMP_AGENT snmp_oid: iso.3.6.1.4.1.21111.1.1.1.3.0 key: upsBasicIdentModel delay: '3600' trends: '0' value_type: CHAR inventory_link: MODEL tags: - tag: Application value: Information - uuid: 50d5a597720d44ceb849a7ea5b2c7588 name: 'UPS name' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.1.5.0 key: upsIdentName delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Information - uuid: 188465763c8d42dd9f543981bce01d35 name: 'UPS software version' type: SNMP_AGENT snmp_oid: 1.3.6.1.4.1.21111.1.1.1.6.0 key: upsIdentUPSSoftwareVersion delay: '3600' trends: '0' value_type: CHAR tags: - tag: Application value: Information dashboards: - uuid: 8b8a04f6e962453694847f6073d75f9b name: Status pages: - widgets: - type: GRAPH_CLASSIC width: '24' height: '5' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'In-out Line Status' host: Stark-3000-snmp - type: GRAPH_CLASSIC 'y': '5' width: '24' height: '5' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'Healt status' host: Stark-3000-snmp - type: GRAPH_CLASSIC 'y': '10' width: '24' height: '5' fields: - type: INTEGER name: source_type value: '0' - type: GRAPH name: graphid value: name: 'Load status' host: Stark-3000-snmp valuemaps: - uuid: 05872cd3d8284425a961814f7f2273dd name: 'STARK Batary status' mappings: - value: '1' newvalue: unknown - value: '2' newvalue: batteryNormal - value: '3' newvalue: batteryLow - value: '4' newvalue: batteryDepleted - value: '5' newvalue: batteryDischarging - value: '6' newvalue: batteryFailure - value: '7' newvalue: batteryReplace - value: '8' newvalue: batterysilence graphs: - uuid: 14064f40e62b4beb9e48d2958f1fcf04 name: 'Healt status' graph_items: - color: 1A7C11 item: host: Stark-3000-snmp key: upsAdvBatteryCapacity - sortorder: '1' color: F63100 item: host: Stark-3000-snmp key: upsAdvBatteryReplaceIndicator - sortorder: '2' color: 2774A4 item: host: Stark-3000-snmp key: upsAdvBatteryActualVoltage - sortorder: '3' color: A54F10 item: host: Stark-3000-snmp key: oid.companymib.upsbattery.upsbatstatus - uuid: f3b1a9a0688341419e3e9a63450ebe3a name: 'In-out Line Status' graph_items: - color: 89ABF8 item: host: Stark-3000-snmp key: upsAdvInputFrequency - sortorder: '1' color: 7EC25C item: host: Stark-3000-snmp key: upsAdvInputLineVoltage - sortorder: '2' color: '274482' item: host: Stark-3000-snmp key: upsAdvOutputFrequency - sortorder: '3' color: 2B5429 item: host: Stark-3000-snmp key: upsAdvOutputVoltage - uuid: f10a859a86a6481b85e1db0a2b3765b5 name: 'Load status' type: STACKED graph_items: - color: 1A7C11 item: host: Stark-3000-snmp key: upsAdvBatteryCapacity - sortorder: '1' color: 2774A4 item: host: Stark-3000-snmp key: upsAdvBatteryActualVoltage - sortorder: '2' color: A54F10 item: host: Stark-3000-snmp key: PresentBypassFrequency - sortorder: '3' color: FC6EA3 item: host: Stark-3000-snmp key: upsAdvOutputCurrent - sortorder: '4' color: 6C59DC item: host: Stark-3000-snmp key: PresentBypassFrequency