5.02021-11-21T21:24:42ZTemplatesSNMP TrippliteSNMP Tripplite## Overview
Updated! Fixed an incorrect OID and refined one of the graphs.
This template was made from scratch for a SU20KRT8 (Using the newest Tripplite MIBs. Zabbix devs, come on and write MIB ingestion into the GUI already.). However, it should support any type of single phase UPS and likely 3 phase.
I may add line discovery in later. But for now this template should cover everything most will need. Including triggers for temp, battery condition, bypass, voltage changes, etc.
Enjoy and please rate!
TemplatesUPS- upsAlarmsPresentSNMP_AGENT.1.3.6.1.2.1.33.1.6.1upsAlarmsPresent30UPS{last()}<>0UPS Alarm PresentWARNING
- upsBatteryStatusSNMP_AGENT.1.3.6.1.2.1.33.1.2.1upsBatteryStatus30UPSAPC Battery Status{last()}<>2Battery Status Not NormalHIGH
- upsBatteryTemperatureSNMP_AGENT.1.3.6.1.2.1.33.1.2.7upsBatteryTemperature60cUPS{last()}>25Battery Temperature Over NominalHIGH
- upsBatteryVoltageSNMP_AGENT.1.3.6.1.2.1.33.1.2.5upsBatteryVoltage60vUPSMULTIPLIER0.1
- upsBypassCurrent.1SNMP_AGENT.1.3.6.1.2.1.33.1.5.3.1.3.1upsBypassCurrent.130AUPSMULTIPLIER0.1
- upsBypassFrequencySNMP_AGENT.1.3.6.1.2.1.33.1.5.1upsBypassFrequency30HzUPS
- upsBypassPower.1SNMP_AGENT.1.3.6.1.2.1.33.1.5.3.1.4.1upsBypassPower.130UPS
- upsBypassVoltage.1SNMP_AGENT.1.3.6.1.2.1.33.1.5.3.1.2.1upsBypassVoltage.130vUPS
- upsEstimatedChargeRemainingSNMP_AGENT.1.3.6.1.2.1.33.1.2.4upsEstimatedChargeRemaining60UPS{last()}<20Battery Charge DepleatedHIGH{last()}<80Battery Charge Less Than 80%WARNING
- upsEstimatedMinutesRemainingSNMP_AGENT.1.3.6.1.2.1.33.1.2.3upsEstimatedMinutesRemaining30mUPS{last()}<10Battery Time Remaining Below 10 MinutesWARNING
- upsIdentAgentSoftwareVersionSNMP_AGENT.1.3.6.1.2.1.33.1.1.4upsIdentAgentSoftwareVersion6000CHARUPS
- upsIdentModelSNMP_AGENT.1.3.6.1.2.1.33.1.1.2upsIdentModel864000CHARUPS
- upsIdentUPSSoftwareVersionSNMP_AGENT.1.3.6.1.2.1.33.1.1.3upsIdentUPSSoftwareVersion6000CHARUPS
- upsInputFrequency.1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.2.1upsInputFrequency.130HzUPS
- upsInputLineBadsSNMP_AGENT.1.3.6.1.2.1.33.1.3.1upsInputLineBads30UPS{last()}<>0UPS Input Power Line BadDISASTER
- upsInputVoltage.1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.1upsInputVoltage.130vUPS{last(#3)}<195 or {last()}>245UPS Power Voltage Outside NominalHIGH
- upsOutputCurrent.1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.1upsOutputCurrent.130AUPSMULTIPLIER0.1
- upsOutputFrequencySNMP_AGENT.1.3.6.1.2.1.33.1.4.2upsOutputFrequency30HzUPS
- upsOutputPercentLoad.1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.5.1upsOutputPercentLoad.130UPS{last(#2)}>49UPS OverloadedHIGH
- upsOutputPower.1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.1upsOutputPower.130wUPS{change()}>300UPS Load ChangedINFO{last()}<1000UPS Low LoadWARNING
- upsOutputSourceSNMP_AGENT.1.3.6.1.2.1.33.1.4.1upsOutputSource30UPSTripplite Output Source{last()}<>3UPS Output Source Not NormalHIGH
- upsOutputVoltage.1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.1upsOutputVoltage.130vUPS
- upsSecondsOnBatterySNMP_AGENT.1.3.6.1.2.1.33.1.2.2upsSecondsOnBattery30sUPS{last()}>30UPS Running On BatteryHIGH
{SNMP Tripplite:upsBypassCurrent.1.last()}<>0 or {SNMP Tripplite:upsBypassPower.1.last()}<>0UPS BypassedWARNINGBatteryNONOSTACKEDDD0000- SNMP TrippliteupsBatteryTemperature
1008800- SNMP TrippliteupsEstimatedChargeRemaining
22774A4- SNMP TrippliteupsEstimatedMinutesRemaining
Current1A7C11- SNMP TrippliteupsBypassCurrent.1
1F63100- SNMP TrippliteupsOutputCurrent.1
VoltageF63100- SNMP TrippliteupsInputVoltage.1
100BB00- SNMP TrippliteupsOutputVoltage.1
APC Battery Status1unknown2batteryNormal3batteryLow4batteryDepletedTripplite Output Source1other2none3normal4bypass5battery6booster7reducer