5.02021-11-25T12:34:44ZTemplates/ModulesYourGroupYourGroup/YourHostTemplate Module ICMP PingTemplate Module ICMP PingTemplate Module ICMP Ping version: 0.12Templates/ModulesStatus- ICMP pingSIMPLEicmpping601wStatusService state{max(#3)}=0Unavailable by ICMP pingHIGHLast value: {ITEM.LASTVALUE1}.
Last three attempts returned timeout. Please check device connectivity.
- ICMP lossSIMPLEicmppingloss601wFLOAT%Status{min(5m)}>{$ICMP_LOSS_WARN} and {min(5m)}<100High ICMP ping lossWARNINGUnavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
- ICMP response timeSIMPLEicmppingsec601wFLOATsStatus{avg(5m)}>{$ICMP_RESPONSE_TIME_WARN}High ICMP ping response timeWARNINGHigh ICMP ping loss{Template Module ICMP Ping:icmppingloss.min(5m)}>{$ICMP_LOSS_WARN} and {Template Module ICMP Ping:icmppingloss.min(5m)}<100Unavailable by ICMP ping{Template Module ICMP Ping:icmpping.max(#3)}=0
{$ICMP_LOSS_WARN}20{$ICMP_RESPONSE_TIME_WARN}0.15UPS - diogontUPS - diogontTemplate Module ICMP PingYourGroupYourGroup/YourHostalarmsInformation(s)Operational- ContactSNMP_AGENTSNMPv2-MIB::sysContact.0sysContact120d0CHARCONTACTInformation(s)
- Software version (full)SNMP_AGENTSNMPv2-MIB::sysDescr.0sysDescr120d0CHAROS_FULLInformation(s)
- Device LocationSNMP_AGENTSNMPv2-MIB::sysLocation.0sysLocation120d0CHARLOCATIONInformation(s)
- Device NameSNMP_AGENTSNMPv2-MIB::sysName.0sysName120d0CHARNAMEInformation(s)
- UptimeSNMP_AGENTSNMPv2-MIB::sysUpTime.0sysUpTime120duptimeInformation(s)MULTIPLIER0.01
- UPS battery capacity (%)SNMP_AGENT.1.3.6.1.2.1.33.1.2.4.0upsAdvBatteryCapacity120dFLOAT%Operational
- UPS battery temperatureSNMP_AGENT.1.3.6.1.2.1.33.1.2.7.0upsAdvBatteryTemperature120d°COperational{last(0)}>27High battery temperature on {HOST.NAME}DISABLEDHIGH
- UPS input current 1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.4.1upsAdvInputCurrent1120dFLOATAOperationalMULTIPLIER0.1{last()}>=200High ups input current 1DISABLEDHIGHTrigger for UPS input current when value is bigger or equal 200.{last()}>=100Information ups input current 1DISABLEDINFOTrigger for UPS input current when value is bigger or equal 100.
- UPS input current 2SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.4.2upsAdvInputCurrent2120dFLOATAOperationalMULTIPLIER0.1{last()}>=200High ups input current 2DISABLEDHIGHTrigger for UPS input current when value is bigger or equal 200.{last()}>=100Information ups input current 2DISABLEDINFOTrigger for UPS input current when value is bigger or equal 100.
- UPS input current 3SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.4.3upsAdvInputCurrent3120dFLOATAOperationalMULTIPLIER0.1{last()}>=200High ups input current 3DISABLEDHIGHTrigger for UPS input current when value is bigger or equal 200.{last()}>=100Information ups input current 3DISABLEDINFOTrigger for UPS input current when value is bigger or equal 100.
- UPS input frequency 1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.2.1upsAdvInputFrequency1120dFLOATHzOperationalMULTIPLIER0.1{last()}>=62
or
{last()}<=57High ups Input Frequency 1DISABLEDHIGHTrigger for UPS input frequency when value is different 60.
- UPS input frequency 2SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.2.2upsAdvInputFrequency2120dFLOATHzOperationalMULTIPLIER0.1{last()}>=62 or {last()}<=57High ups Input Frequency 2DISABLEDHIGHTrigger for UPS input frequency when value is different 60.
- UPS input frequency 3SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.2.3upsAdvInputFrequency3120dFLOATHzOperationalMULTIPLIER0.1{last()}>=62
or
{last()}<=57High ups Input Frequency 3DISABLEDHIGHTrigger for UPS input frequency when value is different 60.
- UPS input power 1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.5.1upsAdvInputPower1120dFLOATWOperational{last()}>130High ups Input PowerDISABLEDHIGH{last()}>80Warning Ups Input PowerDISABLEDWARNING
- UPS input power 2SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.5.2upsAdvInputPower2120dWOperational{last()}>130UPS input power 2DISABLEDHIGH{last()}>=80UPS input power 2DISABLEDWARNING
- UPS input power 3SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.5.3upsAdvInputPower3120dWOperational{last()}>80 or
{last()} < 130UPS input power 3DISABLEDWARNING{last()}>130UPS input power 3DISABLEDHIGH
- UPS input voltage 1SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.1upsAdvInputVoltage1120dFLOATVACOperational{last()}>264
or
{last()}<176High Ups Input voltage 1DISABLEDHIGHTrigger for UPS input voltage when value is bigger than or equal 20% or less than or equal 20%{nodata(600)}=1SNMP Check ConnectLoss: {ITEM.LASTVALUE1}WARNING{last()}>235
or
{last()}<204Warning Ups Input voltage 1DISABLEDWARNINGTrigger for UPS input voltage when value is bigger than or equal 5% or less than or equal 5%
- UPS input voltage 2SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.2upsAdvInputVoltage2120dFLOATVACOperational{last()}>264
or
{last()}<176High Ups Input voltage 2DISABLEDHIGHTrigger for UPS input voltage when value is bigger than or equal 20% or less than or equal 20%{last()}>235 or {last()}<204Warning Ups Input voltage 2DISABLEDWARNINGTrigger for UPS input voltage when value is bigger than or equal 5% or less than or equal 5%
- UPS input voltage 3SNMP_AGENT.1.3.6.1.2.1.33.1.3.3.1.3.3upsAdvInputVoltage3120dFLOATVACOperational{last()}>264
or
{last()}<176High Ups Input voltage 3DISABLEDHIGHTrigger for UPS input voltage when value is bigger than or equal 20% or less than or equal 20%{last()}>235 or {last()}<204Warning Ups Input voltage 3DISABLEDWARNINGTrigger for UPS input voltage when value is bigger than or equal 5% or less than or equal 5%
- UPS output current 1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.1upsAdvOutputCurrent1120dFLOATAOperationalMULTIPLIER0.1
- UPS output current 2SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.2upsAdvOutputCurrent2120dFLOATAOperationalMULTIPLIER0.1
- UPS output current 3SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.3.3upsAdvOutputCurrent3120dFLOATAOperationalMULTIPLIER0.1
- UPS output frequencySNMP_AGENT.1.3.6.1.2.1.33.1.4.2.0upsAdvOutputFrequency120dFLOATHzOperationalMULTIPLIER0.1{last()}>61
or
{last()}<59High ups Output FrequencyDISABLEDHIGHTrigger for UPS output frequency when value is different that 60.
- UPS output load 1 (%)SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.5.1upsAdvOutputLoad1120dFLOAT%Operational{last(0)}>=90Output load 1 Critical on {HOST.NAME}DISABLEDHIGH{last(0)}>=60Output load 1 Information on {HOST.NAME}DISABLEDINFOTrigger for UPS output load when value is bigger or equal 60.
- UPS output load 2 (%)SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.5.2upsAdvOutputLoad2120dFLOAT%Operational{last(0)}>=90Output load 2 Critical on {HOST.NAME}DISABLEDHIGH{last(0)}<=60Output load 2 Information on {HOST.NAME}DISABLEDINFOTrigger for UPS output load when value is bigger or equal 60.
- UPS output load 3 (%)SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.5.3upsAdvOutputLoad3120dFLOAT%Operational{last(0)}>=90Output load 3 Critical on {HOST.NAME}DISABLEDHIGH{last(0)}>=60Output load 3 Information on {HOST.NAME}DISABLEDINFOTrigger for UPS output load when value is bigger or equal 60.
- UPS output power 1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.1upsAdvOutputPower1120dFLOATWOperational
- UPS output power 2SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.2upsAdvOutputPower2120dWOperational
- UPS output power 3SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.4.3upsAdvOutputPower3120dWOperational
- UPS output voltage 1SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.1upsAdvOutputVoltage1120dFLOATVACOperational{last()}>=231
or
{last()}<=209Information UPS output voltage 1DISABLEDHIGHTrigger for UPS output voltage when value is bigger or equal 231 or less than or equal 209..
- UPS output voltage 2SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.2upsAdvOutputVoltage2120dFLOATVACOperational{last()}>=231
or
{last()}<=209Information UPS output voltage 2DISABLEDHIGHTrigger for UPS output voltage when value is bigger or equal 231 or less than or equal 209..
- UPS output voltage 3SNMP_AGENT.1.3.6.1.2.1.33.1.4.4.1.2.3upsAdvOutputVoltage3120dFLOATVACOperational{last()}>=231
or
{last()}<=209Information UPS output voltage 3DISABLEDHIGHTrigger for UPS output voltage when value is bigger or equal 231 or less than or equal 209.
- UPS run time remainingSNMP_AGENT.1.3.6.1.2.1.33.1.2.3.0upsAdvRunTimeRemaining120dmOperational{last(0)}<5Run time remaining CRITICAL on {HOST.NAME}DISABLEDDISASTER{last(0)}<10Run time remaining LOW on {HOST.NAME}DISABLEDHIGH
- UPS Alarm Input BadSNMP_AGENT.1.3.6.1.2.1.33.1.6.3.3upsAlarmInputBad120dalarms
- UPS Alarm Output OverloadSNMP_AGENT.1.3.6.1.2.1.33.1.6.3.8upsAlarmOutputOverload120dalarms
- UPS battery statusSNMP_AGENT.1.3.6.1.2.1.33.1.2.1upsBasicBatteryStatus120dOperationalupsBatteryStatus{last(0)}=3The battery power is too low to support the load on {HOST.NAME}DISABLEDDISASTER
- UPS time on batterySNMP_AGENT1.3.6.1.2.1.33.1.2.2.0upsBasicBatteryTimeOnBattery120dsOperationalMULTIPLIER0.01
UPS Screen430UPS Input Voltage 1UPS - diogont25010000110000030UPS Output Voltage 1UPS - diogont25010010110000030UPS Output Current 1UPS - diogont25010020110000030Battery AutonomyUPS - diogont25010030110000030UPS Input Voltage 2UPS - diogont25010001110000030UPS output voltage 2UPS - diogont25010011110000030UPS Output Current 2UPS - diogont25010021110000030Battery CapacityUPS - diogont25010031110000030UPS Input Voltage 3UPS - diogont25010002110000030UPS output voltage 3UPS - diogont25010012110000030UPS Output Current 3UPS - diogont2501002211000003Battery Autonomy300NONO1GRADIENT_LINEFFA726ALLGRAPH_SUM- UPS - diogontupsAdvRunTimeRemaining
Battery Capacity200NONO1GRADIENT_LINE78909CALL- UPS - diogontupsAdvBatteryCapacity
Battery statusFIXEDBOLD_LINEC80000- UPS - diogontupsBasicBatteryStatus
UPS CurrentFIXEDBOLD_LINEB71C1C- UPS - diogontupsAdvInputCurrent1
1BOLD_LINE4444FF- UPS - diogontupsAdvOutputCurrent1
UPS FrequencyFIXEDGRADIENT_LINEFF4000- UPS - diogontupsAdvOutputFrequency
UPS Input Voltage 1150NONOSTACKEDFIXED1GRADIENT_LINE43A047- UPS - diogontupsAdvInputVoltage1
UPS Input Voltage 2300NONOFIXED1GRADIENT_LINE43A047- UPS - diogontupsAdvInputVoltage2
UPS Input Voltage 3300NONOFIXED1GRADIENT_LINE43A047ALL- UPS - diogontupsAdvInputVoltage2
UPS LoadFIXEDFIXEDGRADIENT_LINE4444FF- UPS - diogontupsAdvOutputLoad1
UPS Output Current 1400NONOSTACKED1GRADIENT_LINEFFA726- UPS - diogontupsAdvOutputCurrent1
UPS Output Current 2400NONOSTACKED1GRADIENT_LINEFFA726- UPS - diogontupsAdvInputCurrent2
UPS Output Current 3400FIXED1GRADIENT_LINEFFA726ALL- UPS - diogontupsAdvInputCurrent3
UPS Outputs Currents600FIXED1BOLD_LINE4444FF- UPS - diogontupsAdvOutputCurrent1
2FFA726- UPS - diogontupsAdvOutputCurrent2
3FF9800- UPS - diogontupsAdvOutputCurrent3
UPS Outputs Voltages600FIXED1BOLD_LINE2196F3- UPS - diogontupsAdvOutputVoltage1
21E88E5- UPS - diogontupsAdvOutputVoltage2
31565C0- UPS - diogontupsAdvOutputVoltage3
UPS Output Voltage 1400NONO1GRADIENT_LINE2196F3ALL- UPS - diogontupsAdvOutputVoltage1
UPS output voltage 2400NONO1GRADIENT_LINE2196F3- UPS - diogontupsAdvOutputVoltage2
UPS output voltage 3400NONO1GRADIENT_LINE2196F3- UPS - diogontupsAdvOutputVoltage3
UPS PowerFIXEDBOLD_LINEB71C1C- UPS - diogontupsAdvInputPower1
1BOLD_LINE4444FF- UPS - diogontupsAdvOutputPower1
UPS TemperatureFIXEDGRADIENT_LINEFF0000- UPS - diogontupsAdvBatteryTemperature
Service state0Down1UpupsBatteryStatus1unknown2batteryNormal3batteryLow4batteryDepleted