5.02021-11-21T21:51:50ZCoolingAPC InRow CoolingAPC InRow Cooling## Overview
This template is for use with APC InRow Cooling Units. There are 4 Applications, 25 Items, 6 Triggers, and 3 Graphs.
* Applications:
+ Information
+ Return Side
+ Supply Side
+ Thresholds
* Items:
+ Airflow
+ Condensate Pump Run hours
+ Cooling Demand Power
+ Cooling output Power
+ Cool Set Point
+ Dehumidify/Output
+ Dew Point
+ Discharge Pressure
+ Fan Speed
+ Humidifier Run Hours
+ Humidify Output
+ Operating Mode
+ Return Side:
- Air Temo
- Sire Temp Threshold
- Humudty
- Humidity High and Low Thresholds
+ Suction Pressure
+ Suction Temp
+ Supply Side:
- Set Point
- Air Temp
- Air Temp Threshold
- Humidity
+ System Name
+ System Up Time
* Triggers
+ Return Humidity High and Low
+ Return Temp Critical and High
+ Supply Temp High
The Triggers are formed using the thresholds set by the APC InRow cooling system setup. The values are pulled from the MIB and stored as Item. This was more efficient when developing the triggers for use with multiple Cooling Units.
All the Intervals and History values can be changed per your desired use. Thank you for downloading and using this template.
## Author
Chad Hoye
CoolingInformationReturn SideSupply SideThresholds- Fan SpeedSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.5coolingUnitConfigurationAnalogDescription.1.510s30dFLOAT%MULTIPLIER.1
- Supply Air Temp ThresholdSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3.1.3coolingUnitConfigurationAnalogValue.1.31d30dFLOATFThresholdsMULTIPLIER.1
- Return Air Temp ThresholdSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3.1.5coolingUnitConfigurationAnalogValue.1.51d10dFLOATFThresholdsMULTIPLIER.1
- Return Humidity Low ThresholdSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3.1.7coolingUnitConfigurationAnalogValue.1.71d10dFLOAT%RHThresholdsMULTIPLIER.1
- Return Humidity High ThresholdSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3.1.8coolingUnitConfigurationAnalogValue.1.81d10dFLOAT%RHThresholdsMULTIPLIER.1
- Cool Set PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3.1.9coolingUnitConfigurationAnalogValue.1.91d30dFLOATFInformationMULTIPLIER0.1
- Supply Air Set PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3.1.12coolingUnitConfigurationAnalogValue.1.1210s30dFLOATFSupply SideMULTIPLIER0.1
- AirflowSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.3coolingUnitStatusAnalogValue.1.310s30dFLOATCFMMULTIPLIER0.001
- Supply Air TempSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.6coolingUnitStatusAnalogValue.1.610sFLOATFSupply SideMULTIPLIER.1
- Return Air TempSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.8coolingUnitStatusAnalogValue.1.810s30dFLOATFReturn SideMULTIPLIER.1
- Supply HumiditySNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.10coolingUnitStatusAnalogValue.1.1010s30dFLOAT%RHSupply SideMULTIPLIER.1
- Return HumiditySNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.11coolingUnitStatusAnalogValue.1.1110s30dFLOAT%RHReturn SideMULTIPLIER.1
- Cooling Demand PowerSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.12coolingUnitStatusAnalogValue.1.1230s30dFLOATkWMULTIPLIER.1
- Cooling Output PowerSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.13coolingUnitStatusAnalogValue.1.1330s30dFLOATkWMULTIPLIER.1
- Dehumidify OutputSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.16coolingUnitStatusAnalogValue.1.1610s30dFLOAT%Rh
- Humidify OutputSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.18coolingUnitStatusAnalogValue.1.1810s30dFLOAT%Rh
- Suction TempSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.21coolingUnitStatusAnalogValue.1.2110s30dFLOATFMULTIPLIER0.1
- Suction PressureSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.22coolingUnitStatusAnalogValue.1.2210s30dFLOATPSIMULTIPLIER0.1
- Discharge PressureSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.24coolingUnitStatusAnalogValue.1.2410s30dFLOATPSIMULTIPLIER0.1
- Humidifier Run HrsSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.38coolingUnitStatusAnalogValue.1.381h30dFLOATHrsMULTIPLIER.1
- Condensate Pump Run HrsSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.39coolingUnitStatusAnalogValue.1.391h30dFLOATHrsMULTIPLIER.01
- Dew PointSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3.1.49coolingUnitStatusAnalogValue.1.4910s30dFLOATFMULTIPLIER.1
- Operating ModeSNMP_AGENT.1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.3.1.2coolingUnitStatusDiscreteIntegerAsString.1.21h30d0TEXTInformation
- System NameSNMP_AGENT.1.3.6.1.2.1.1.5.0sysName.01d30d0TEXTInformation
- System Up TimeSNMP_AGENT.1.3.6.1.2.1.1.3.0sysUpTime.01h30dFLOATuptimeInformationMULTIPLIER0.01
{APC InRow Cooling:coolingUnitStatusAnalogValue.1.11.avg(5m)}>={APC InRow Cooling:coolingUnitConfigurationAnalogValue.1.8.last()}RECOVERY_EXPRESSION{APC InRow Cooling:coolingUnitStatusAnalogValue.1.11.avg(1m)}<{APC InRow Cooling:coolingUnitConfigurationAnalogValue.1.8.last()}Return Humidity High {HOST.NAME}WARNINGYES{APC InRow Cooling:coolingUnitStatusAnalogValue.1.11.avg(5m)}<={APC InRow Cooling:coolingUnitConfigurationAnalogValue.1.7.last()}RECOVERY_EXPRESSION{APC InRow Cooling:coolingUnitStatusAnalogValue.1.11.avg(1m)}>{APC InRow Cooling:coolingUnitConfigurationAnalogValue.1.7.last()}Return Humidity Low {HOST.NAME}WARNINGYES({APC InRow Cooling:coolingUnitStatusAnalogValue.1.8.avg(5m)})>{APC InRow Cooling:coolingUnitConfigurationAnalogValue.1.5.last()}RECOVERY_EXPRESSION({APC InRow Cooling:coolingUnitStatusAnalogValue.1.8.avg(5m)})<{APC InRow Cooling:coolingUnitConfigurationAnalogValue.1.5.last()}Return Temp High {HOST.NAME}HIGHYES({APC InRow Cooling:coolingUnitStatusAnalogValue.1.6.avg(5m)})>{APC InRow Cooling:coolingUnitConfigurationAnalogValue.1.3.last()}RECOVERY_EXPRESSION({APC InRow Cooling:coolingUnitStatusAnalogValue.1.6.avg(5m)})<{APC InRow Cooling:coolingUnitConfigurationAnalogValue.1.3.last()}Supply Temp High {HOST.NAME}HIGHYESAir TempNOE65100- APC InRow CoolingcoolingUnitStatusAnalogValue.1.8
1303F9F- APC InRow CoolingcoolingUnitStatusAnalogValue.1.6
HumidityF9A825- APC InRow CoolingcoolingUnitStatusAnalogValue.1.11
10277BD- APC InRow CoolingcoolingUnitStatusAnalogValue.1.10