zabbix_export: version: '6.0' date: '2021-11-21T21:22:23Z' groups: - uuid: 7df96b18c230490a9a0a9e2307226338 name: Templates templates: - uuid: fbf34d5c284845eda09455d5a6523c57 template: 'SNMP APC NetBotz Rack Monitor 200' name: 'SNMP APC NetBotz Rack Monitor 200' description: | ## Overview LLD of Sensors (Only Temperature and humidity) Trigger Prototypes for recommended 45RH% - 55RH% humidity and 20°C - 24°C Temperature Graph Prototypes for Temperature and Humidity. Triggers names contain the last value that cause the trigger so you can see the temp/hum in the alert. groups: - name: Templates discovery_rules: - uuid: 8e14be382c704b04b5a509ea44a2f1ac name: 'Internal APC Sensor' type: SNMP_AGENT snmp_oid: 'discovery[{#SNMPVALUE},1.3.6.1.4.1.318.1.1.10.4.2.3.1.3.0]' key: apc.enviro.sensor delay: '30' item_prototypes: - uuid: a466796ddaf747e89f7c275dae63719e name: '{#SNMPVALUE} Sensor Humidity' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.10.4.2.3.1.6.0.1 key: 'apc.enviro.sensor.int.hum.["{#SNMPINDEX}"]' delay: '30' units: '%RH' tags: - tag: Application value: 'Environment Monitor' trigger_prototypes: - uuid: 8fd2bb17859941c886c7c43a82a8b706 expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.["{#SNMPINDEX}"])>55' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 55 RH%' priority: HIGH dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH%' expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.["{#SNMPINDEX}"])>=60' - uuid: 69cd7c0eaa604f768c0d9c12f48d7105 expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.["{#SNMPINDEX}"])>=60' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidity > 60 RH%' priority: DISASTER - uuid: ac1baae828a5409e906c960cdee769f9 expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.["{#SNMPINDEX}"])<45' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidiy< 45 RH%' priority: HIGH dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH%' expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.["{#SNMPINDEX}"])<=40' - uuid: bfc78d874e6b4af0a1bc47af0250c548 expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.hum.["{#SNMPINDEX}"])<=40' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Humidty < 40 RH%' priority: DISASTER - uuid: 372429e0233c41afa4faa547b8b1f68c name: '{#SNMPVALUE} Sensor Temperature' type: SNMP_AGENT snmp_oid: .1.3.6.1.4.1.318.1.1.10.4.2.3.1.5.0.1 key: 'apc.enviro.sensor.int.temp.["{#SNMPINDEX}"]' delay: '30' units: °C tags: - tag: Application value: 'Environment Monitor' trigger_prototypes: - uuid: 28d252062a6943688c364d5cdf5e7fd6 expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.["{#SNMPINDEX}"])<=15' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 15°C' priority: HIGH dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C' expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.["{#SNMPINDEX}"])<=19' - uuid: 047898627a3b40aa8d70bd469ef45997 expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.["{#SNMPINDEX}"])<=19' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature < 19°C' priority: WARNING - uuid: b491b6812b8948ca8048230a712912d7 expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.["{#SNMPINDEX}"])>=22' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 22°C' priority: WARNING dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C' expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.["{#SNMPINDEX}"])>=24' - uuid: 1f18535d936d4f0f862b0c1bb61d45dc expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.["{#SNMPINDEX}"])>=24' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 24°C' priority: HIGH dependencies: - name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C' expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.["{#SNMPINDEX}"])>=30' - uuid: 37093f763c7d4f4d9b1ffae94f4b2bdd expression: 'last(/SNMP APC NetBotz Rack Monitor 200/apc.enviro.sensor.int.temp.["{#SNMPINDEX}"])>=30' name: '{#SNMPVALUE} {ITEM.LASTVALUE} :: Temperature > 30°C' priority: DISASTER graph_prototypes: - uuid: bc1b8a9cb56e4631b17fff881a604ebc name: 'Temp/Hum {#SNMPVALUE}' graph_items: - color: 1A7C11 item: host: 'SNMP APC NetBotz Rack Monitor 200' key: 'apc.enviro.sensor.int.hum.["{#SNMPINDEX}"]' - sortorder: '1' color: F63100 item: host: 'SNMP APC NetBotz Rack Monitor 200' key: 'apc.enviro.sensor.int.temp.["{#SNMPINDEX}"]'