5.02021-11-21T21:40:02ZTemplatesSNMP-iDRAC-9SNMP-iDRAC-9## Description
Lucas Afonso Kremer https://www.linkedin.com/in/lucasafonsokremer
## Overview
**Template for Dell servers with iDRAC 9 controller.**
------------------------------------------------------
* #### Tested on PowerEdge R440 with version 3.21.21.21
* #### The value maps are available to download on 3.0 version, please import this template first
* #### You must add one macro on the server or on the template with the name:
{$SNMP\_COMMUNITY} with the community to be used
* #### All the items was created with "SNMPv2 agent"
* #### Make sure your iDRAC is reachable from the zabbix server/proxy, test with:
snmpstatus -v 2c -c public 192.168.0.1 Based on @endersonmaia iDRAC 7 template
## Author
Lucas Afonso Kremer
TemplatesFansMemoryNetwork CardsPowerStorage and disksSystem InfoTemperaturesVoltages- BIOS DateSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.300.50.1.7.1.1BiosDate1d30d0CHARSystem Info
- BIOS VersionSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.300.50.1.8.1.1BiosVersion1d30d0CHARSystem Info
- CMOS Battery StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.50.1.5.1.1CMOSBatteryStatus1h30dSystem InfoDell Open Manage System Status{last(0)}<>3{HOST.NAME}: Problem with CMOS BatteryWARNINGYES
- Overall System LCD StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.2.2.0GlobalSystemLCDStatus1h30dSystem InfoDell Open Manage System Status
- Overall System Power StateSNMP_AGENT1.3.6.1.4.1.674.10892.5.2.4.0GlobalSystemPowerState1h30dPowerDellPowerState{last(0)}<>4 and {last(0)}<>0{HOST.NAME}: System is not onlineHIGHYES
- Overall System StatusSNMP_AGENT.1.3.6.1.4.1.674.10892.5.2.1.0GlobalSystemStatus5m30dSystem InfoDell Open Manage System Status{nodata(600)}{HOST.NAME}: No iDrac data for 10 minutesHIGHYES({last()}<>3) and ({last()}<5){HOST.NAME}: Overall System Status ErrorWARNINGYES({last()}>4){HOST.NAME}: Overall System Status ErrorDISASTERYES
- Overall System Storage StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.2.3.0GlobalSystemStorageStatus1h30dStorage and disksDell Open Manage System Status{last(0)}<>3{HOST.NAME}: Storage System Status ErrorWARNINGYES{HOST.NAME}: RAID Controller Error({SNMP-iDRAC-9:RAIDControllerStatus.last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4)
- DRAC Access URLSNMP_AGENT1.3.6.1.4.1.674.10892.2.1.1.7.0idrac_acessurl1d30d0CHARSystem Info
- System Asset TagSNMP_AGENT1.3.6.1.4.1.674.10892.2.1.1.11.0idrac_assettag1d30d0CHARASSET_TAGSystem Info
- System Express Service CodeSNMP_AGENT1.3.6.1.4.1.674.10892.5.1.3.3.0idrac_esc1d30d0CHARSystem Info
- DRAC Firmware versionSNMP_AGENT1.3.6.1.4.1.674.10892.2.1.1.5.0idrac_firmwareversion1d30d0CHARSystem Info
- System ModelSNMP_AGENT1.3.6.1.4.1.674.10892.5.1.3.12.0idrac_SystemModel1d30d0CHARSystem Info
- DRAC versionSNMP_AGENT1.3.6.1.4.1.674.10892.2.1.1.2.0idrac_version1d30d0CHARSystem Info
- Power Usage Minimum Idle PowerSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.60.1.15.1.1PowerUsageMinIdle1h30dWPower
- Power Usage Sensor StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.60.1.5.1.1PowerUsageSensorStatus1h30dPowerDell Open Manage System Status
- RAID Controller : Firmware VersionSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.1.1.8.1RAIDControllerFirmware1d30d0CHARStorage and disks
- RAID Controller : NameSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.1.1.2.1RAIDControllerName1d30d0CHARStorage and disks
- RAID Controller : StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.1.1.37.1RAIDControllerStatus10m30dStorage and disksDell Open Manage System Status
- System BIOS StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.300.50.1.5.1.1SystemBiosStatus1h30dSystem InfoDell Open Manage System Status
- System Power StateSNMP_AGENT1.3.6.1.4.1.674.10892.5.2.4.0SystemPowerState5m30d0CHAR4 server is on
3 server is on stand-byPower
- Voltage Status CombinedSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.200.10.1.12.1VoltageStatusCombined10m30dVoltagesDell Open Manage System Status
Disk EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.2]DiskEnumeration1dDisk {#SNMPINDEX} : Manufacture DaySNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.32.{#SNMPINDEX}DiskManufactureDay.[{#SNMPINDEX}]1d1w90dStorage and disksDisk {#SNMPINDEX} : ManufacturerSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.3.{#SNMPINDEX}DiskManufacturer.[{#SNMPINDEX}]1d30d0CHARStorage and disksDisk {#SNMPINDEX} : Manufacture WeekSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.33.{#SNMPINDEX}DiskManufactureWeek.[{#SNMPINDEX}]1d30d90dStorage and disksDisk {#SNMPINDEX} : Manufacture YearSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.34.{#SNMPINDEX}DiskManufactureYear.[{#SNMPINDEX}]1d30d90dStorage and disksDisk {#SNMPINDEX} : Model NumberSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.6.{#SNMPINDEX}DiskModel.[{#SNMPINDEX}]1d0CHARStorage and disksDisk {#SNMPINDEX} : NameSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.55.{#SNMPINDEX}DiskName.[{#SNMPINDEX}]1d0CHARStorage and disksDisk {#SNMPINDEX} : Serial NumberSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.7.{#SNMPINDEX}DiskSerialNo.[{#SNMPINDEX}]1d0CHARStorage and disksDisk {#SNMPINDEX} : Disk SizeSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.11.{#SNMPINDEX}DiskSize.[{#SNMPINDEX}]1d1w90dBStorage and disksMULTIPLIER1048576Disk {#SNMPINDEX} : Disk StateSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.4.{#SNMPINDEX}DiskState.[{#SNMPINDEX}]1h1w90dStorage and disksDellDracDiskStateDisk {#SNMPINDEX} : Disk StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.130.4.1.24.{#SNMPINDEX}DiskStatus.[{#SNMPINDEX}]1h1w90dStorage and disksDell Open Manage System Status({SNMP-iDRAC-9:DiskStatus.[{#SNMPINDEX}].last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Problem with Disk {#SNMPINDEX}DISASTERFan EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.4.700.12.1.8.1]FanEnumeration1dFan {#SNMPVALUE} SpeedSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.700.12.1.6.1.{#SNMPINDEX}FanSpeed.[{#SNMPINDEX}]5m2d90drpmFansFan {#SNMPVALUE} StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.700.12.1.5.1.{#SNMPINDEX}FanStatus.[{#SNMPINDEX}]5m2d90dFansDell Open Manage System Status({SNMP-iDRAC-9:FanStatus.[{#SNMPINDEX}].last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Problem with FAN {#SNMPVALUE}AVERAGEFAN {#SNMPVALUE}C80000- SNMP-iDRAC-9FanSpeed.[{#SNMPINDEX}]
Memory EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.4.1100.50.1.8.1]MemoryEnum1d;50s/1-7,00:00-24:00Memory Slot {#SNMPVALUE} ManufacturerSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.50.1.21.1.{#SNMPINDEX}MemManufacturer[{#SNMPINDEX}]1d0CHARMemoryMemory Slot {#SNMPVALUE} Part NumberSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.50.1.22.1.{#SNMPINDEX}MemPartlNo.[{#SNMPINDEX}]1d0CHARMemoryMemory Slot {#SNMPVALUE} Serial NumberSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.50.1.23.1.{#SNMPINDEX}MemSerialNo.[{#SNMPINDEX}]1d0CHARMemoryMemory Slot {#SNMPVALUE} SizeSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.50.1.14.1.{#SNMPINDEX}MemSize.[{#SNMPINDEX}]1d0BMemoryMULTIPLIER1024Memory Slot {#SNMPVALUE} SpeedSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.50.1.15.1.{#SNMPINDEX}MemSpeed.[{#SNMPINDEX}]1d0nsMemoryMemory Slot {#SNMPVALUE} StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.50.1.5.1.{#SNMPINDEX}MemStatus.[{#SNMPINDEX}]30m1w90dMemoryDell Open Manage System Status({SNMP-iDRAC-9:MemStatus.[{#SNMPINDEX}].last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Problem with memory in slot {#SNMPVALUE}HIGHNetwork EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.4.1100.90.1.2.1]NetworkEnum1dNIC {#SNMPINDEX} : Connection StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.90.1.4.1.{#SNMPINDEX}NetConnStatus.[{#SNMPINDEX}]10m2d90dNetwork CardsDell iDRAC Network Device Connection StatusNIC {#SNMPINDEX} : MAC AddressSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.90.1.15.1.{#SNMPINDEX}NetMAC.[{#SNMPINDEX}]1d0CHARNetwork CardsNIC {#SNMPINDEX} : NameSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.90.1.6.1.{#SNMPINDEX}NetName.[{#SNMPINDEX}]1d0CHARNetwork CardsNIC {#SNMPINDEX} : SlotSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.90.1.30.1.{#SNMPINDEX}NetSlot.[{#SNMPINDEX}]1d0CHARNetwork CardsNIC {#SNMPINDEX} : StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.90.1.3.1.{#SNMPINDEX}NetStatus.[{#SNMPINDEX}]5m2d90dNetwork CardsDell Open Manage System Status({SNMP-iDRAC-9:NetStatus.[{#SNMPINDEX}].last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Error on NIC {#SNMPINDEX}DISASTERPower Supply EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.4.600.12.1.1.1]PowerSupplies1dPower Supply {#SNMPINDEX} Input VoltageSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.12.1.9.1.{#SNMPINDEX}PowerSupplyInputVoltage.[{#SNMPINDEX}]5m2d90dFLOATVPowerPower Supply {#SNMPINDEX} Maximum PowerSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.12.1.6.1.{#SNMPINDEX}PowerSupplyMaxPower.[{#SNMPINDEX}]1d2d90dFLOATWPowerMULTIPLIER.1Power Supply {#SNMPINDEX} Sensor StateSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.12.1.11.1.{#SNMPINDEX}PowerSupplySensorState.[{#SNMPINDEX}]10m2d90dPowerDell_PSU_SensorStatePower Supply {#SNMPINDEX} State SettingsSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.12.1.4.1.{#SNMPINDEX}PowerSupplyStateSettings.[{#SNMPINDEX}]10m2d90dPowerDell PSU State SettingsPower Supply {#SNMPINDEX} StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.12.1.5.1.{#SNMPINDEX}PowerSupplyStatus.[{#SNMPINDEX}]5m2d90dPowerDell Open Manage System Status({SNMP-iDRAC-9:PowerSupplySensorState.[{#SNMPINDEX}].last(0)}<>1) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Error on PSU {#SNMPINDEX} StateHIGH({SNMP-iDRAC-9:PowerSupplyStatus.[{#SNMPINDEX}].last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Problem with PSU {#SNMPINDEX}HIGHProcessor EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.4.1100.32.1.7.1]ProcEnum1dProcessor {#SNMPINDEX} StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.1100.32.1.5.1.{#SNMPINDEX}ProcStatus.[{#SNMPINDEX}]5m2d90dSystem InfoDell Open Manage System Status({SNMP-iDRAC-9:ProcStatus.[{#SNMPINDEX}].last(0)}<>3) and ({SNMP-iDRAC-9:ProcStatus.[{#SNMPINDEX}].last(0)}<>2) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Error on Processor {#SNMPINDEX}DISASTERYESTemperature EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.4.700.20.1.8.1]TempEnum1dTemperature Sensor {#SNMPVALUE} Critical Low-LimitSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.700.20.1.13.1.{#SNMPINDEX}TempCritLowLimit.[{#SNMPINDEX}]1d0FLOATCTemperaturesMULTIPLIER0.1Temperature Sensor {#SNMPVALUE} Critical Up-LimitSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.700.20.1.10.1.{#SNMPINDEX}TempCritUpLimit.[{#SNMPINDEX}]1d0FLOATCTemperaturesMULTIPLIER0.1Temperature Sensor {#SNMPVALUE} StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.700.20.1.5.1.{#SNMPINDEX}TempStatus.[{#SNMPINDEX}]5m2d90dTemperaturesDell Open Manage System Status{last(0)}<>3Problem with Temperature Sensor {#SNMPVALUE}WARNINGTemperature Sensor {#SNMPVALUE} ValueSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.700.20.1.6.1.{#SNMPINDEX}TempValue.[{#SNMPINDEX}]5m2d90dFLOATCTemperaturesDell Open Manage System StatusMULTIPLIER.1Temperature Sensor {#SNMPVALUE} Warning Low-LimitSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.700.20.1.12.1.{#SNMPINDEX}TempWarnLowLimit.[{#SNMPINDEX}]1d0FLOATCTemperaturesMULTIPLIER0.1Temperature Sensor {#SNMPVALUE} Warning Up-LimitSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.700.20.1.11.1.{#SNMPINDEX}TempWarnUpLimit.[{#SNMPINDEX}]1d0FLOATCTemperaturesMULTIPLIER0.1{SNMP-iDRAC-9:TempValue.[{#SNMPINDEX}].last()} >= {SNMP-iDRAC-9:TempCritUpLimit.[{#SNMPINDEX}].last()}Temperature on {#SNMPVALUE} critically highHIGHTemperature of the item is above Critical Level.{SNMP-iDRAC-9:TempValue.[{#SNMPINDEX}].last()} <= {SNMP-iDRAC-9:TempCritLowLimit.[{#SNMPINDEX}].last()}Temperature on {#SNMPVALUE} critically lowHIGHTemperature of the item is below Critical Level.{SNMP-iDRAC-9:TempValue.[{#SNMPINDEX}].last()} > {SNMP-iDRAC-9:TempWarnUpLimit.[{#SNMPINDEX}].last()}
and
{SNMP-iDRAC-9:TempValue.[{#SNMPINDEX}].last()} < {SNMP-iDRAC-9:TempCritUpLimit.[{#SNMPINDEX}].last()}Temperature on {#SNMPVALUE} to highWARNINGTemperature of the item is above Warning Level.{SNMP-iDRAC-9:TempValue.[{#SNMPINDEX}].last()} < {SNMP-iDRAC-9:TempWarnLowLimit.[{#SNMPINDEX}].last()}
and
{SNMP-iDRAC-9:TempValue.[{#SNMPINDEX}].last()} > {SNMP-iDRAC-9:TempCritLowLimit.[{#SNMPINDEX}].last()}Temperature on {#SNMPVALUE} to lowWARNINGTemperature of the item is below Warning Level.Temperature on sensor {#SNMPVALUE}C80000ALL- SNMP-iDRAC-9TempValue.[{#SNMPINDEX}]
Voltage Table EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.4.600.20.1.8.1]VoltageTable1dVoltage : {#SNMPVALUE} StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.4.600.20.1.5.1.{#SNMPINDEX}VoltageStatus.[{#SNMPINDEX}]10m1w90dVoltagesDell Open Manage System Status({SNMP-iDRAC-9:VoltageStatus.[{#SNMPINDEX}].last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Error on Voltage Sensor {#SNMPVALUE}AVERAGEDisk Volume EnumerationSNMP_AGENTdiscovery[{#SNMPVALUE},1.3.6.1.4.1.674.10892.5.5.1.20.140.1.1.1]VolumeEnum1dVolume {#SNMPINDEX} : Virtual Disk StateSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.140.1.1.4.{#SNMPINDEX}VolumeDiskState.[{#SNMPINDEX}]1h0Storage and disksDellRaidVolumeStateVolume {#SNMPINDEX} : NameSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.140.1.1.36.{#SNMPINDEX}VolumeName.[{#SNMPINDEX}]1d0CHARStorage and disksVolume {#SNMPINDEX} : SizeSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.140.1.1.6.{#SNMPINDEX}VolumeSize.[{#SNMPINDEX}]1d0BStorage and disksMULTIPLIER1048576Volume {#SNMPINDEX} : StateSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.140.1.1.13.{#SNMPINDEX}VolumeState.[{#SNMPINDEX}]1h0Storage and disksDellRaidLevelVolume {#SNMPINDEX} : StatusSNMP_AGENT1.3.6.1.4.1.674.10892.5.5.1.20.140.1.1.20.{#SNMPINDEX}VolumeStatus.[{#SNMPINDEX}]1h0Storage and disksDell Open Manage System Status({SNMP-iDRAC-9:VolumeDiskState.[{#SNMPINDEX}].last(0)}<>2) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Volume {#SNMPINDEX} ErrorHIGH({SNMP-iDRAC-9:VolumeStatus.[{#SNMPINDEX}].last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Volume {#SNMPINDEX} Status ErrorHIGH({SNMP-iDRAC-9:RAIDControllerStatus.last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: RAID Controller ErrorHIGHYES({SNMP-iDRAC-9:GlobalSystemStorageStatus.last(0)}>4) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Storage System Status ErrorDISASTERYES({SNMP-iDRAC-9:VoltageStatusCombined.last(0)}<>3) and ({SNMP-iDRAC-9:SystemPowerState.last(0)}=4){HOST.NAME}: Voltage Status ErrorHIGHYESDellDracDiskState1Unknown2Ready3Online4Foreign5Offline6Blocked7Failed8Non-RAID9RemovedDell iDRAC Network Device Connection Status1Down2UpDell Open Manage System Status1Other2Unknown3OK4NonCritical5Critical6NonRecoverableDellPowerState1Other2Unknown3Off4OnDell PSU State Settings1Unknown2Online (state disabled)4not Ready8Fan Failure10Online and Fan Failure16On242Online and OKDellRaidLevel1Unknown2RAID-03RAID-14RAID-55RAID-66RAID-107RAID-508RAID-609Concatenated RAID 110Concatenated RAID 5DellRaidVolumeState1Unknown2Online3Failed4DegradedDell_PSU_SensorState1Presence Detected2PS Failure4Predictuve Failure8PS AC lost16AC lost or out of range32AC out of range but still present