zabbix_export: version: '5.4' date: '2021-11-21T21:24:27Z' groups: - uuid: 7df96b18c230490a9a0a9e2307226338 name: Templates templates: - uuid: 538ca25742a24d149c960e4f7730d8c1 template: 'IPMI Dell PowerEdge 2950' name: 'IPMI Dell PowerEdge 2950' description: | ## Overview Template IPMI Dell PowerEdge 2950 ## Author Chinge_Yang groups: - name: Templates items: - uuid: 3146d7f276de4b9ca9bc09066426ea30 name: 'Ambient Temp' type: IPMI key: ipmi.ambient.temp delay: '300' history: 7d value_type: FLOAT units: ℃ ipmi_sensor: 'Ambient Temp' tags: - tag: Application value: 'Temperature Sensors' triggers: - uuid: e929a7a4da4a48d8905825782688b283 expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.ambient.temp)<=3) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.ambient.temp)<=8)' name: 'Ambient Temp temperature lower critical on {HOSTNAME}' priority: HIGH - uuid: 1fd460946bac4448827dc2e1054cc3d6 expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.ambient.temp)<=8) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.ambient.temp)<=13)' name: 'Ambient Temp temperature lower non-critical on {HOSTNAME}' priority: AVERAGE - uuid: f5158fc0ec9b465a8bfc25ef8e8d5977 expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.ambient.temp)>=47) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.ambient.temp)>=42)' name: 'Ambient Temp temperature upper critical on {HOSTNAME}' priority: HIGH - uuid: d265939a87da484ebd71e056d683aadb expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.ambient.temp)>=42) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.ambient.temp)>=37)' name: 'Ambient Temp temperature upper non-critical on {HOSTNAME}' priority: AVERAGE - uuid: 249626661bcd4226b20e7cdcf36a08d1 name: 'FAN 1 RPM' type: IPMI key: ipmi.fan.1.rpm delay: '300' history: 7d units: RPM ipmi_sensor: 'FAN 1 RPM' tags: - tag: Application value: 'Fans Sensors' triggers: - uuid: 7a01b57a4682480fbbaff75a1b1a1dd7 expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.1.rpm)<=1275) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.1.rpm)<=1395)' name: 'FAN 1 RPM lower critical on {HOSTNAME}' priority: HIGH - uuid: 331b6137760049d58786e491024c54e9 name: 'FAN 2 RPM' type: IPMI key: ipmi.fan.2.rpm delay: '300' history: 7d units: RPM ipmi_sensor: 'FAN 2 RPM' tags: - tag: Application value: 'Fans Sensors' triggers: - uuid: 07aeb7756c3c467ca826636f289dcb76 expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.2.rpm)<=1275) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.2.rpm)<=1395)' name: 'FAN 2 RPM lower critical on {HOSTNAME}' priority: HIGH - uuid: a3b82b8d67464cb6b0bfc6c1b6e2a975 name: 'FAN 3 RPM' type: IPMI key: ipmi.fan.3.rpm delay: '300' history: 7d units: RPM ipmi_sensor: 'FAN 3 RPM' tags: - tag: Application value: 'Fans Sensors' triggers: - uuid: 8d0fc54a138c46e390d956b151065c69 expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.3.rpm)<=1275) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.3.rpm)<=1395)' name: 'FAN 3 RPM lower critical on {HOSTNAME}' priority: HIGH - uuid: 565788e33e2f44ada58ea10072ca487c name: 'FAN 4 RPM' type: IPMI key: ipmi.fan.4.rpm delay: '300' history: 7d units: RPM ipmi_sensor: 'FAN 4 RPM' tags: - tag: Application value: 'Fans Sensors' triggers: - uuid: caf4d7c6490840c0b3d3e11dc7a3eb2c expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.4.rpm)<=1275) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.4.rpm)<=1395)' name: 'FAN 4 RPM lower critical on {HOSTNAME}' priority: HIGH - uuid: 2e1947d397b54887a25591309f382d0f name: 'FAN 5 RPM' type: IPMI key: ipmi.fan.5.rpm delay: '300' history: 7d units: RPM ipmi_sensor: 'FAN 5 RPM' tags: - tag: Application value: 'Fans Sensors' triggers: - uuid: 2899f7ce3e9d4e3aaa912b1a08664f7e expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.5.rpm)<=1275) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.5.rpm)<=1395)' name: 'FAN 5 RPM lower critical on {HOSTNAME}' priority: HIGH - uuid: cf56bc32ebf9401393815d41bd311a29 name: 'FAN 6 RPM' type: IPMI key: ipmi.fan.6.rpm delay: '300' history: 7d units: RPM ipmi_sensor: 'FAN 6 RPM' tags: - tag: Application value: 'Fans Sensors' triggers: - uuid: 9334006995d7454893652b53a7aca434 expression: '({TRIGGER.VALUE}=0 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.6.rpm)<=1275) or ({TRIGGER.VALUE}=1 and last(/IPMI Dell PowerEdge 2950/ipmi.fan.6.rpm)<=1395)' name: 'FAN 6 RPM lower critical on {HOSTNAME}' priority: HIGH - uuid: 4fa2467b2daf4b6fa7ab915aa83d0975 name: Power type: IPMI key: power delay: '300' history: 7d ipmi_sensor: power valuemap: name: 'Service state' tags: - tag: Application value: 'Power Supply' triggers: - uuid: bb7e4e8f3ca34096a13a23f73d20f683 expression: 'last(/IPMI Dell PowerEdge 2950/power)=0' name: 'Power status changed on {HOSTNAME}' priority: HIGH valuemaps: - uuid: a831c610a9fa4ea49523ba14e9c9d9c8 name: 'Service state' mappings: - value: '0' newvalue: Down - value: '1' newvalue: Up graphs: - uuid: 7a1fde1d19ee4b0ab800b874d0bcb8bb name: 'Fan speed & temperature' graph_items: - color: 00C800 item: host: 'IPMI Dell PowerEdge 2950' key: ipmi.fan.1.rpm - sortorder: '1' color: C80000 item: host: 'IPMI Dell PowerEdge 2950' key: ipmi.fan.2.rpm - sortorder: '2' color: 0000C8 yaxisside: RIGHT item: host: 'IPMI Dell PowerEdge 2950' key: ipmi.ambient.temp