5.02021-11-21T21:23:23ZTemplatesIPMI Intel RMM3IPMI Intel RMM3## Overview
IntelĀ® Remote Management Module 3
Sensors:
* 1 | BB +1.05V PCH | Voltage
* 2 | BB +1.1V P1 Vccp | Voltage
* 3 | BB +1.5V P1 DDR3 | Voltage
* 4 | BB +3.3V | Voltage
* 5 | BB +3.3V STBY | Voltage
* 6 | BB +5.0V | Voltage
* 7 | Baseboard Temp1 | Temperature
* 8 | Baseboard Temp2 | Temperature
* 9 | Front Panel Temp | Temperature
* 11 | Sys Fan Tach 1A | Fan
* 12 | Sys Fan Tach 1B | Fan
* 13 | Sys Fan Tach 2A | Fan
* 14 | Sys Fan Tach 2B | Fan
* 15 | Sys Fan Tach 3A | Fan
* 16 | Sys Fan Tach 3B | Fan
* 17 | PS Power In | Other Units Based Sensor
4 Triggers
note: Authentication algorithm - md5
TemplatesFanIPMI SensorsPowerTemperatureVoltage- Baseboard Temp1IPMIrmm3.Baseboard_Temp130CBaseboard Temp1IPMI SensorsTemperature{last()}<9 or {last()}>60Baseboard Temp1 [{ITEM.VALUE}]HIGH
- Baseboard Temp2IPMIrmm3.Baseboard_Temp230CBaseboard Temp2IPMI SensorsTemperature{last()}<9 or
{last()}>60Baseboard Temp2 [{ITEM.VALUE}]HIGH
- BB +1.05V PCHIPMIrmm3.BB_plus1.05V_PCH30FLOATVBB +1.05V PCHIPMI SensorsVoltage
- BB +1.1V P1 VccpIPMIrmm3.BB_plus1.1V_P1_Vccp30FLOATVBB +1.1V P1 VccpIPMI SensorsVoltage
- BB +1.5V P1 DDR3IPMIrmm3.BB_plus1.5V_P1_DDR330FLOATVBB +1.5V P1 DDR3IPMI SensorsVoltage
- BB +3.3VIPMIrmm3.BB_plus3.3V30FLOATVBB +3.3VIPMI SensorsVoltage
- BB +3.3V STBYIPMIrmm3.BB_plus3.3V_STBY30FLOATVBB +3.3V STBYIPMI SensorsVoltage
- BB +5.0VIPMIrmm3.B_plus5.0V30FLOATVBB +5.0VIPMI SensorsVoltage
- Front Panel TempIPMIrmm3.Front_Panel_Temp30CFront Panel TempIPMI SensorsTemperature
- PS Power InIPMIrmm3.PS_Power_In30WPS Power InIPMI SensorsPower{last()}=0Power is off on {HOST.NAME}AVERAGE
- Sys Fan Tach 1AIPMIrmm3.Sys_Fan_Tach_1A30RPMSys Fan Tach 1AFanIPMI Sensors
- Sys Fan Tach 1BIPMIrmm3.Sys_Fan_Tach_1B30RPMSys Fan Tach 1BFanIPMI Sensors
- Sys Fan Tach 2AIPMIrmm3.Sys_Fan_Tach_2A30RPMSys Fan Tach 2AFanIPMI Sensors
- Sys Fan Tach 2BIPMIrmm3.Sys_Fan_Tach_2B30RPMSys Fan Tach 2BFanIPMI Sensors
- Sys Fan Tach 3AIPMIrmm3.Sys_Fan_Tach_3A30RPMSys Fan Tach 3AFanIPMI Sensors
- Sys Fan Tach 3BIPMIrmm3.Sys_Fan_Tach_3B30RPMSys Fan Tach 3BFanIPMI Sensors
{IPMI Intel RMM3:rmm3.Sys_Fan_Tach_1A.last()}<1000
or
{IPMI Intel RMM3:rmm3.Sys_Fan_Tach_1B.last()}<1000
or
{IPMI Intel RMM3:rmm3.Sys_Fan_Tach_2A.last()}<1000
or
{IPMI Intel RMM3:rmm3.Sys_Fan_Tach_2B.last()}<1000
or
{IPMI Intel RMM3:rmm3.Sys_Fan_Tach_3A.last()}<1000
or
{IPMI Intel RMM3:rmm3.Sys_Fan_Tach_3B.last()}<1000Low fan speed on {HOST.NAME}WARNING